IM DA100-11E
6-2
6.1 Setting Command
Setting the strain input
Setting SRp1, p2, p3, p4, p5<terminator>
p1 Channel number (001 to 560)
p2 STRAIN
p3 Measurement range
2k/20k/200k
p4 Left value of span
p5 Right value of span
Example Set the measurement range of subunit 1 and
channel 01 to 20k, left value of span to 0, and
right value of span to 100.
SR101, STRAIN, 20k, 0, 100
Comments Even when the settings of p3 are the same
parameters, the measurement range of the strain
varies depending on the gauge method. For
details, refer to page 5-7.
Set spans, p4 and p5, within the measurement
range indicated in page 5-7.
Input values within 6 digits disregarding the
decimal point for p4 and p5.
The measurement range cannot be changed
while executing a report or computation.
Setting the pulse input
Setting SRp1, p2, p3, p4, p5, p6, p7, p8, p9<terminator>
p1 Channel number (001 to 560)
p2 PULSE
p3 Measuring mode
RATE momentary pulse count mode
GATE contact ON/OFF detection mode
p4 Left value of span (0 to 30000)
p5 Right value of span (0 to 30000)
p6 Left value of scale (0 to 30000)
p7 Right value of scale (0 to 30000)
p8 Decimal point position of scale (0 to 4)
p9 Filter (ON or OFF)
Example Set subunit 1 and channel 01 to momentary pulse
count mode, left value of span to 0, and right value
of span to 1000.
SR101, PULSE, RATE, 0, 1000, 0, 1000, 0
Comments When omitting p6, p7, or p8, omit all three.
When summing the count number or the ON
time, set the computational expression with the
SO command, then execute computation start
with the EX command. When the pulse input
module is installed, the use of computation
channels become available without the math
option. However, the only computational
expression available in this case is
TLOG.PSUM(XXX) for summing the count
number or the ON time.
The measurement range cannot be changed
while executing a report or computation.
Setting Scaling
Setting SRp1, p2, p3, p4, p5, p6, p7, p8, p9<terminator>
p1 Channel number (001 to 560)
p2 SCL
p3 Type of input
VOLT DC voltage
TC Thermocouple
RTD Resistance temperature detector
DI Contact
p4 Measurement range
p5 Left value of span
p6 Right value of span
p7 Left value of scale (-30000 to 30000)
p8 Right value of scale (-30000 to 30000)
p9 Decimal point position of scale (0 to 4)
Example Change channel 02 of subunit 0 to an input in
which 1 V is converted to 0.00 and 5 V to 100.00.
SR002, SCL, VOLT, 6V, 1000, 5000, 0, 10000,
2
Comments For the p4 measurement range, see the range
parameter table on Pages 5-6 and 5-7.
For the p5 and p6 setting spans, set them in the
ranges shown in the setting range on Pages 5-6
and 5-7.
For p5 and p6 setting values, enter them within
6 digits excluding the decimal point.
Select either to set all three parameters, p7, p8
and p9, or to omit them all.
The measurement range cannot be changed
while executing a report or computation.
Setting the power monitor scaling
Setting SRp1, p2, p3, p4, p5,...., p11<terminator>
p1 Channel number (001 to 560)
p2 SCL
p3 AC
p4 Wiring method
1Ph2W: Single-phase two-wire system
1Ph3W: Single-phase three-wire system
(only on a three-wire system)
3Ph3W-2I: Three-phase three-wire system
(only on a two-voltage two-
current three-wire system)
3Ph3W-3I: Three-phase three-wire system
(only on a three-voltage three-
current three-wire system)
3Ph4W: three-phase four-wire system
(only on a three-wire system)
p5 Input range
25 V - 0.5 A
25 V - 5 A
250 V - 0.5 A
250 V - 5 A
p6 Measurement item
p7 Left value of span
p8 Right value of span
p9 Left value of scale (-30000 to 30000)
p10 Right value of scale (-30000 to 30000)
p11 Decimal point position of scale (0 to 4)
Example Measure the active power on subunit 0 and channel
01, and convert 10W to 0.00 and 100W to 100.00.
SR001, SCL, AC, 3Ph3W-2I, 250V-0.5A,
P1, 10, 100, 000, 10000, 2
Comments Settings of p4 and p5 are common within one
power monitor module. If the setting is
changed, the settings on other channels also
change.
For the measurement item p6, refer to the list
of measurement items on page 5-9.
There are items that can not be set on the
measurement item, p6, depending on the wiring
method or the settings on other channels. Set
within the group indicated on page 5-9.
Set the span values, p7 and p8, within the
measurement range indicated on page 5-7.
Input values within 6 digits disregarding the
decimal point for p7 and p8. The decimal point
position is fixed to the decimal point position
of the setting range of page 5-7.
For p9, p10, and p11, either set all the three
parameters or omit all three.