IM DA100-01E
2-15
2
Installation and Wiring
1 Verify that the power switch of the DA100/DS400/DS600 has been turned OFF.
2 Remove the terminal cover. (the figure below shows DU100-11.)
Terminal cover
Screws for fastenin
g
the cover
3 Fasten the signal wires to the terminals as shown in the figure below.
4 Re-apply the terminal cover and fasten the screws.
Note
Make sure that the equipment connected to the signal in-/output conforms IEC (CSA) 950 or IEC (CSA)
1010. Also, make sure to use cables conform IEC (CSA) standards.
In case you are using an internal RJC in case of thermocouple input, the following considerations are
necessary to stabilize the temperature at the terminals. Always make sure to re-apply the terminal cover;
The thermal capacity of the wiring should be small (cross sectional area of less than 0.5mm
2
); Minimize
outside temperature fluctuations as much as possible.
To prevent noise, make sure to ground each unit at the grounding function terminal (below the power
switch) together at one point.
Refrain from wiring the input signals parallel. However, if you do, then the following considerations are
necessary. Ground all equipment at the same point; Do not turn the power of other equipment ON/OFF
during operation; Do not use the burnout function.
If communication is disrupted while outputting the value of the communication input channel from the
retransmission module, the retransmission module holds the value that was output immediately before the
disruption occurred.
After the power is turned ON or the retransmission or input channel settings are changed, it may take
apporoximately twice teh measurement interval (amount of time needed to make two measurements) for
the value of the retransmission to be stabilized.
When a computation error or a burnout occurs, the output voltage or current will be the +OVER level
or the -OVER level depending on the Set Up mode settings.
The maximum time that takes to search out a burnout by using the universal input module or the DCV/
TC/DI input module is 2.5 seconds. The values being output during this period from the transmission
output module are unstable if a burnout occurs.
2.6 Connecting the Signal Lines