- 82/131 -
IM MW100-S16E-1
Ed01
Table 39. Parameters for configuring polling period of DNP client
Kind Configuration
Client
Function
Enabling switch of DNP client function
- toggle switch to Enable or not
Integrity Poll
Period for polling static data
- configurable within 1 to 3600 [s]
Event Poll
Period for polling event data
- configurable within 1 to 3600 [s]
Response
Timeout
Limit of waiting time for the response corresponding to the command
- configurable within 1 to 60 [s]
- When response is not received over the limit,
DNP client will send the next command.