Table 12. Parameters for configuring mapping information
Kind Configuration
Function Publishing function codes for accessing DNP objects
- selectable from “Off”, “Poll”, “Read”, “Select + Operate”,
“Direct Operate”, “Direct Operate, NR”
Slave / Server Table number of the destination
- selectable from "01" to "10"
Object Group Group number of the DNP object in the target
- configurable within 0 to 255
Object Variation Variation number of the DNP object in the target
- configurable within 0 to 255
Object Index Index number of the DNP object in the target
- configurable within 0 to 65535
Channel Top Top channel of MW100 which exchange data with DNP objects
- selectable within 001 to 060, A001 to A300 or C001 to C300
Channel Count Channel count of MW100 which exchange data with DNP objects
- configurable within :
1 to 60 when 001 to 060 is set to top channel,
1 to 300 when 'A' or 'C' channel is set to top channel