Yokogawa Standalone MW100 Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 131
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
- 30/131 -
IM MW100-S16E-1
Ed01
Polling objects and the setting of group number field in command table of DNP
master/client functions are shown in Table 13.
Table 13. Polling objects and setting of group number
Object Group Purpose
Binary Input (1)
Binary Input Event (2)
1 Polling static and event data of
Binary Input objects
Double-bit (3)
Double-bit Event (4)
3 Polling static and event data of
Double-bit objects
Binary Output (10)
Binary Output Event (11)
10 Polling static and event data of
Binary Output objects
Counter (20)
Counter Event (22)
20 Polling static and event data of
Counter objects
Analog Input (30)
Analog Input Event (32)
30 Polling static and event data of
Analog Input objects
Analog Output (40)
Analog Output Event (42)
40 Polling static and event data of
Analog Output objects