The Read Message on Rung 0002 is configured as shown below……
Message Type CIP Data Table Read
Source Element real[1000] (DX Advanced Measurement Channel 0)
Number of Elements 10
Destination Element Tag DX_Advanced_Measurement_Channels (Array Tag, Real format)
The Message Read instruction is configured as follows……
Click on the Message instruction ―View Configuration Dialog‖ button
In the ―Configuration area, select the Message Type (CIP Data Table Read), select the Source Element tag (real[1000]),
enter the Number of Elements (10), and the Destination Element (DX_Advanced_Measurement_Channels). Then click on
the ―Communication‖ tab.
Enter the ―Path‖ information. In this case the Ethernet port on the Compact Logix is used which would be
―LocalENB,2,192.168.001.100 (the ―2‖ is the communication depth on the Compact Logix). Select ―Connected‖ and
―Cache Connections‖ (speeds up communications). Click ―OK‖. The DX Advanced Read Message configuration is
complete.
25