Yokogawa Data Acquisition with PID Control CX2000 Manuel d'utilisateur Page 24

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 59
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 23
24 IM 04L31A01-02E
2.
Press the #1 soft key (Control action, Input setting).
3.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure, and press the DISP/ENTER key.
Select 1
Select Single
Select Temp
4.
Press the ESC key to return to the basic control setting menu.
5.
Press the #3 soft key (Output processing).
6.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure, and press the DISP/ENTER key.
Select 1
Select On/Off-control
* No need to set
Cycle time and
Analog-output type
7.
Press the ESC key twice to return to the menu display (basic setting mode 2/2).
8.
Press the End soft key.
A window appears for you to confirm the saving of the new settings.
9.
Press the DISP/ENTER key to confirm the settings.
Setting the Control Input Range in Setting Mode
1.
From the operation display, click the MENU key to display the control setting menu
shown below.
Examples of Control Setup Operation
Vue de la page 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 58 59

Commentaires sur ces manuels

Pas de commentaire