Yokogawa Integral Oxygen Analyzer ZR202 Manuel d'utilisateur Page 105

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 169
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 104
IM 11M13A01-04E
8-17
8. Detailed Data Setting
For liquid fuel
Amount of water vapor in exhaust gas (Gw) = (1/100) {1.24 (9h + w)} [m /kg]
Theoretical amount of air (Ao) = {(12.38 / 10000) x H1}
2
1.36 [m /kg]
Low calorific power = H1
X value = {(3.37 / 10000) x Hx}
2
2.55 [m
3
/kg]
where, H1: low calorific power of fuel
h: Hydrogen in fuel (weight %)
w: Moisture content in fuel (weight %)
Hx: Same as numeric value of H1
For gaseous fuel
Amount of water vapor in exhaust gas = (1/100) {(h2) + 1/2 Sy (Cy hy) + w} [m /m ]
Theoretical amount of air = 11.2 x (H1/10000) [m /m ]
Low calorific power = H1
X value = (1.05 / 10000) x Hx [m /m ]
where, H1: low calorific power of fuel
h: Hydrogen in fuel (weight %)
w: Moisture content in fuel (weight %)
Hx: Same as numeric value of H1
For solid fuel
Amount of water vapor in exhaust gas (Gw) = (1/100) {1.24 (9h + w)} [m /kg]
Theoretical amount of air = {(1.01 x (H1 / 1000)} + 0.56 [m /kg]
Low calorific power = H1 = Hh
2
25 (9h + w) [kJ/kg]
X value = 1.11 - (0.106 / 1000 ) x Hx [m /m ]
where, w: Total moisture content in use (weight %)
h: Hydrogen content (weight %)
The average hydrogen content of coal mined in Japan, which is a dry ash-free type, is
5.7 %. Accordingly, "h" may be expressed mathematically by:
h = 5.7 [{100
2
(w + a)} / 100] x (100
2
w) / (100
2
w1)
where, a: Ash content [%]
w1: Moisture content [%], analyzed on a constant humidity basis
Hh: Higher calorific power of fuel [kJ/kg]
H1: Low calorific power of fuel [kJ/kg]
Hx: Same numeric value of H1
3
3
3
3
3
3
3
3
3
3
3
3
Figure 8.3 Fuel Calculation Formula
Vue de la page 104
1 2 ... 100 101 102 103 104 105 106 107 108 109 110 ... 168 169

Commentaires sur ces manuels