3.10 Counting Pulses (/PM1 option)
This section explains how to use computation channels to count pulses that are received
from pulse input terminals.
For an explanation of this function, see section 1.2.
Display
Press MENU and then select > Menu tab > Math channel > Calculation expression,
Alarm.
Settings
First-CH, Last-CH
Select the target channels.
Math range > Math On/Off
Select On.
Math range > Calculation expression
You can use the following variables in equations.
Q01 to Q08: The number of pulses per second.
P01 to P08: The number of pulses per scan interval.
* The numbers 01 to 08 refer to the pulse input terminal numbers.
For computation channel conguration instructions, see section 10.1.
There are examples on the next page to help explain conguration options.