Communication (Ethernet) > FTP client
Setting Selectable Range or Choices Default Value
FTP transfer file
Disp&Event data On/Off Off
Report On/Off Off
Snapshot On/Off Off
FTP connection Primary/Secondary Primary
FTP server name Character string (up to 64 characters)
Port number Numeric value (0 to 65535) 21
Login name Character string (up to 32 characters)
Password Character string (up to 32 characters) ******...***
Account Character string (up to 32 characters)
PASV mode On/Off Off
Initial path Character string (up to 64 characters)
Communication (Ethernet) > SNTP client
Setting Selectable Range or Choices Default Value
SNTP client
Use/Not Use/Not Not
Server name Character string (up to 64 characters)
Port number Numeric value (0 to 65535) 123
Access interval Off/1h/8h/12h/24h 8h
Access reference time Numeric value (00: 00 to 23: 59) 00: 00
Access timeout 10s/30s/90s 30s
Time adjust on Start action On/Off Off
Communication (Ethernet) > Modbus client > Basic settings
Setting Selectable Range or Choices Default Value
Modbus client basic settings
Read cycle 125ms/250ms/500ms/1s/2s/5s/10s 1s
Retry interval Off/10s/20s/30s/1min/2min/5min/10min/20min/30min/1h 2min
Communication (Ethernet) > Modbus client > Modbus server settings
Setting Selectable Range or Choices Default Value
Server number 1-8/9-16 1-8
Modbus server settings
Port number Numeric value (0 to 65535) 502
Modbus server name Character string (up to 64 characters)
Unit Auto/Fixed Auto
No. 0 to 255 1
Communication (Ethernet) > Modbus client > Command settings
Setting Selectable Range or Choices Default Value
Client command number 1-8/9-16 1-8
1 to 16 Off/R/R-M/W/W-M Off
Client settings > First Varies depending on the send command type
Client settings > Last Varies depending on the send command type
Server settings > Server 1/2/3/…/15/16 1
Server settings > Registers Numeric value (register number)
R, R-M:30001
W, W-M: 40001
Server settings > Type INT16/UINT16/INT32_B/INT32_L/UINT32_B/
R, R-M, W: INT16
UINT32_L/FLOAT_B/FLOAT_L
W-M: INT32_B
Default MV2000 Settings