IM 1E10C1-E
7-16
7. OPERATION VIA HART COMMUNICATOR
(5) Power Frequency (For DC version only)
In case of DC power supply version, setting power frequency is required in area where
the frequency differs. The meter is set to 50.00Hz at the factory.
1. Device setup 4. Detailed setup 2. Input 4. Signal procesing 4. Power freq
ADMAG SE :
Power freq
50.00
50.00
DEL DEL ESC ENTER
1
2
Enter “60.00” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
ADMAG SE :
Signal processing
1 Rate limit
2 Dead time
3 Power synch
4 Power freq 60.00
HELP SEND HOME ENTER
3
Call up “Power freq” setting display.
‘60.00’
ADMAG SE :
Power freq
50.00
60.00
DEL DEL ESC ENTER
Example: Set “60.00”.
4. Power freq
F4
(ENTER)
F2
(SEND)
IMPORTANT