Yokogawa ADMAG AXF Manuel d'utilisateur Page 28

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 107
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 27
IM 1E10C1-E
5-9
5. FUNCTION AND DATA SETTINGS
5.5.2 Display of Internal Totalization Values
By setting a weight per a pulse, flow rate totalized value is shown on the display of
the converter.
(1) Setting Totalization Pulse Weight
Example: To output 10 liter per pulse in flow rate span of  m
3
/h.
Set the pulse weight unit in parameter No. “E01”.
When pulses are to be output per some liter with the flow
rate span of
■■
m
3
/h, select “02” since L = 10
-3
× m
3
Set the pulse weight “10(l)” in parameter No. “E02”.
Set the low cut range nearby 0% in parameter No. “E03”.
Setting Range: 0 to 100% (of span)
The flow rate totalized value calculation can be set in
parameter No. “n01” by selecting “NO DAMPING” or
DAMPING”.
Display Description
Volume UnitCode
00
01
02
03
04
05
06
Default : 3%
Default : 01
Defalt : 06
(Damped flow rate value)
Volume unit in that for the flow rate span ×10
-9
Volume unit in that for the flow rate span ×10
-6
Volume unit in that for the flow rate span ×10
-3
Volume unit in that for the flow rate span ×1
Volume unit in that for the flow rate span ×10
3
Volume unit in that for the flow rate span ×10
6
Number of pulses output per second at 100%
output
Vue de la page 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 106 107

Commentaires sur ces manuels

Pas de commentaire