Yokogawa EJA530A Manuel d'utilisateur Page 39

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 67
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 38
IM 01C21F01-01E
8-8
8. BRAIN TERMINAL BT200 OPERATION
b. Setting Calibration Range Lower
Range Value and Higher Range Value
(C21: LOW RANGE, C22: HIGH
RANGE)
These range values are set as specified in the order
before the instrument is shipped. Follow the proce-
dure below to change the range.
• The measurement span is determined by the high
and low range limit values. In this instrument,
changing the low range value also automatically
changes the high range value, keeping the span
constant.
• Example 1: With present settings of 0 to 30 kPa,
set the lower range value to 0.5 kPa.
Span = Higher range value – Lower range value
FEED NO OK
SET
C21:LOW RANGE
0.5 kPa
DATA DIAG PRNT ESC
SET
C20:PRESS UNIT
kPa
C21:LOW RANGE
0.5 kPa
C22:HIGH RANGE
30.5 kPa
DEL CLR ESC
SET
C21:LOW RANGE
0 kPa
+ 0.5
The higher range value is changed
while the span remains constant.
Set 0.5.
Press the key twice to
enter the setting.
Press the (OK) key.
F0813.EPS
• Note, however, that changing the higher range value
does not cause the lower range value to change.
Thus, changing the higher range value also changes
the span.
• Calibration range can be specified with range value
specifications up to 5 digits (excluding any decimal
point) for low or high range limits within the range
of –32000 to 32000.
• Example 2: With present settings of 0 to 30 kPa,
set the Higher range value to10 kPa.
FEED NO OK
SET
C22:HIGH RANGE
10 kPa
DATA DIAG PRNT ESC
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
C22:HIGH RANGE
10 kPa
DEL CLR ESC
SET
C22:HIGH RANGE
30 kPa
+ 10
The low range value is not
changed, so the span changes.
Set 10.
Press the key twice
to enter the setting.
F0814.EPS
Press the (OK) key.
(3) Damping Time Constant Setup
(C30: AMP DAMPING)
When the instrument is shipped, the damping time
constant is set at 2.0 seconds. Follow the procedure
below to change the time constant.
• Example: Change from 2.0 sec to 4.0 sec.
ESC
SET
C30:AMP DAMPING
4.0 sec
FEED NO OK
SET
C30:AMP DAMPING
2.0 sec
< 2.0 sec >
< 4.0 sec >
< 8.0 sec >
< 16.0 sec >
Use the or key to
select 4.0 sec.
Press the key twice to
enter the setting.
F0815.EPS
0.2sec
0.5sec
1.0sec
2.0sec
4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
Press the (OK) key.
Note: The damping time constant set here is the damping time
constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values for
the amplifier assembly and for the capsule assembly. For the
capsule assembly damping time constant (fixed), see the
“General Specifications” found at the end of this manual.
(See Chapter 10.)
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 66 67

Commentaires sur ces manuels

Pas de commentaire