Yokogawa Electric Corporation
AXF
Magnetic Flowmeter
Integral Flowmeter/
Remote Flowtube
[Hardware Edition]
IM 01E20D01-01E
IM 01E20D01-01E
10th Edition
Vue de la page 0
1 2 3 4 5 6 ... 132 133

Résumé du contenu

Page 1 - IM 01E20D01-01E

User’sManualYokogawa Electric CorporationAXFMagnetic FlowmeterIntegral Flowmeter/Remote Flowtube[Hardware Edition]IM 01E20D01-01EIM 01E20D01-01E10th E

Page 2 - Contents

IM 01E20D01-01E2-22. HANDLING PRECAUTIONS2.3 Storage PrecautionsIf the instrument is to be stored for a long period oftime after delivery, observe th

Page 3 - CONTENTS

IM 01E20D01-01E6-386. OUTLINE AXF Standard, AXF150, AXF200, Wafer Type, Ceramics Lining150150(6)C232(9.13)214(8.43)144(5.67)254(10.00)378(14.88)20.2

Page 4 - 1. INTRODUCTION

IM 01E20D01-01E6-396. OUTLINE AXF Standard, AXF002-AXF015, JIS/ANSI/DIN Flange Type, PFA Lininig*1: When indicator code N is selected, subtract 12

Page 5 - Flowmeter Safely

IM 01E20D01-01E6-406. OUTLINE AXF Standard, AXF025-AXF050, JIS/ANSI/DIN Flange Type, PFA /Polyurethane Rubber /Natural SoftRubber /EPDM Rubber Linin

Page 6 - Converters

IM 01E20D01-01E6-416. OUTLINE AXF Standard, AXF065-AXF125, JIS/ANSI/DIN Flange Type, PFA /Polyurethane Rubber /Natural SoftRubber /EPDM Rubber Linin

Page 7 - 1.4 ATEX Documentation

IM 01E20D01-01E6-426. OUTLINE AXF Standard, AXF150, AXF200, JIS/ANSI/DIN Flange Type, PFA /Polyurethane Rubber /Natural SoftRubber /EPDM Rubber Lini

Page 8 - 1. INTRODUCTION

IM 01E20D01-01E6-436. OUTLINE AXF Standard, AXF250-AXF400, JIS/ANSI/DIN Flange Type, PFA /Polyurethane Rubber /Natural SoftRubber /EPDM Rubber Linin

Page 9 - 2. HANDLING PRECAUTIONS

IM 01E20D01-01E6-446. OUTLINE AXF Standard, AXF015-AXF125, Sanitary for Clamp Connection, PFA Lining28(1.1)51.551.5(2.03) (2.03)HrH148(1.89)70(2.76)

Page 10 - Precautions

IM 01E20D01-01E6-456. OUTLINE AXF Standard, AXF015-AXF125, Sanitary for Union Connection, PFA LiningIntegral Flowmeter Remote Flowtube Integral Flow

Page 11 - 3. INSTALLATION

IM 01E20D01-01E6-466. OUTLINE AXF Standard, AXF015-AXF125, Sanitary for Butt Weld, PFA Lining51.5(2.03)(2.03)51.5197(7.76)*128(1.1)66*1Hr48(1.89)70(

Page 12 - IMPORTANT

IM 01E20D01-01E6-476. OUTLINE Replacement model for Earlier ADMAG or ADMAG AE, AXF002-AXF015, Wafer Type, PFA LiningDHi49(1.93)73(2.87)HrH1ø86(3.38)

Page 13 - 3.2 Handling Precautions

IM 01E20D01-01E3-13. INSTALLATION3. INSTALLATIONBased on JIS B7554 "Electromagnetic Flowmeters"and our piping condition test data, we recom

Page 14 - 3.3 Mounting Procedures

IM 01E20D01-01E6-486. OUTLINE Replacement model for Earlier ADMAG or ADMAG AE, AXF150, AXF200, Wafer Type,PFA /Polyurethane Rubber Lining*4: D, E, F

Page 15

IM 01E20D01-01E6-496. OUTLINE Replacement model for Earlier ADMAG or ADMAG AE, AXF150-AXF250, JIS/ANSI/DIN Flange Type,PFA /Polyurethane Rubber Lini

Page 16 - F0309b.EPS

IM 01E20D01-01E6-506. OUTLINE AXF Standard, AXF500-AXF10L, JIS/ANSI/DIN Flange Type, Polyurethane Rubber LiningCJ1(JIS10K) CG1(JIS F12)*1Max. Height

Page 17 - F0310c.EPS

IM 01E20D01-01E6-516. OUTLINE AXF Standard, AXF11L-AXF13L, JIS Flange Type, Polyurethane Rubber Lining*1: The value before the gasket is tightened.*

Page 18

IM 01E20D01-01E6-526. OUTLINE AXF Standard, AXF16L-AXF26L, JIS Flange Type, Polyurethane Rubber LiningCG1(JIS F12)L1IntervaløRHole dia.PQTIntervalYL

Page 19 - 3. INSTALLATION

IM 01E20D01-01E6-536. OUTLINE Unless otherwise specified, difference in the dimensions are refer to the following table.Above Equal or below Above E

Page 20

IM 01E20D01-01E7-17. PED (PRESSURE EQUIPMENT DIRECTIVE)7. PED (PRESSURE EQUIPMENT DIRECTIVE)This chapter describes further requirements and noticesco

Page 21 - F0312c.EPS

IM 01E20D01-01E8-18. EXPLOSION PROTECTED TYPE INSTRUMENT8. EXPLOSION PROTECTED TYPEINSTRUMENTIn this section, further requirements and differences fo

Page 22

IM 01E20D01-01E8-28. EXPLOSION PROTECTED TYPE INSTRUMENTMaximum surface temperature:T0802.EPSMaximum Surface Temperature+85°C (+185°F)+130°C (+266°F)

Page 23

IM 01E20D01-01E8-38. EXPLOSION PROTECTED TYPE INSTRUMENT(Remote Flowtube)WARNING• De-energize before opening.• Take care not to generate mechanical s

Page 24 - T0313-02.EPS

IM 01E20D01-01E3-23. INSTALLATIONF0302.EPS(Incorrect)Upstream side(Correct)Downstream sideFigure 3.1.2 Chemical Injection(5) Precautions for Use of L

Page 25

IM 01E20D01-01E8-48. EXPLOSION PROTECTED TYPE INSTRUMENT8.2 FM(1) Technical Data*AXF002C – AXF400CApplicable Standard:FM3600, FM3610, FM3615,FM3810,

Page 26 - Flange ratings

IM 01E20D01-01E8-58. EXPLOSION PROTECTED TYPE INSTRUMENTConduitMagnetic FlowmeterSealing FittingHAZARDOUS LOCATIONS18" (457 mm) Max.F0802.EPSFig

Page 27 - T0315.EPS

IM 01E20D01-01E8-68. EXPLOSION PROTECTED TYPE INSTRUMENTTemperature Code:T0808.EPSTemperatureCodeMaximum Process Temperature–40°C (–40°F)–40°C (–40°F

Page 28

IM 01E20D01-01E8-78. EXPLOSION PROTECTED TYPE INSTRUMENT8.4 IECExWARNINGOnly trained persons use this instrument inindustrial locations.(1) Technical

Page 29

IM 01E20D01-01E8-88. EXPLOSION PROTECTED TYPE INSTRUMENT(3) Operation(Integral Flowmeter)WARNING• After de-energizing, delay 20 minutes beforeopening

Page 30

IM 01E20D01-01E8-98. EXPLOSION PROTECTED TYPE INSTRUMENTUo=250V*, Io=3.37mA*, Po=0.211W*Uo and Io are rms value.• Ignition and Explosion Class of gas

Page 31 - Tab.3.3.19.EPS

IM 01E20D01-01E8-108. EXPLOSION PROTECTED TYPE INSTRUMENTFlameproof packing adapterWiring metalconduitFlexible metal conduitTeeDrain plugF0810.EPSApp

Page 32 - 3.3.6 Sanitary Type

EX-B03E1INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENTINSTALLATION AND OPERATING PRECAUTIONS FORTIIS FLAMEPROOF EQUIPMENTApparat

Page 33

EX-B03E2INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT4. Installation of FlameproofApparatus(1) Installation AreaFlameproof appa

Page 34 - T0502.EPS

EX-B03E3INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT6. Maintenance of FlameproofApparatusTo maintain the flameproof apparatus,

Page 35 - 4. WIRING

IM 01E20D01-01E3-33. INSTALLATION• Mounting orientationIMPORTANTIf electrodes are perpendicular to the ground, airbubbles near the top or precipitate

Page 36 - F0401.EPS

IM 01E20D01-01EEdition Date Page Revised Item6th Oct. 2005 3-22 to 3-24 Added the "Confirmation of adapter mounting screw"5-1 (7) Added the

Page 37 - 4.1.4 Wiring Connections

IM 01E20D01-01EEdition Date Page Revised Item8th Apr. 2007 1-2 (4) Changed the warning note of "Maintenance".1-5 1.4 Added the ATEX document

Page 38

IM 01E20D01-01EEdition Date Page Revised Item10th June 2012 1-3 Added the "Trademarks".2-1 2.2 Deleted the fuse from item of accessories.3-1

Page 39 - F0410.EPS

IM 01E20D01-01E6-33 Corrected the sentence of /MU.6-34 Changed the selectable range of flow rate span for optional code"SC".6-43 Correced th

Page 40 - F0413.EPS

IM 01E20D01-01E3-43. INSTALLATION(4) Terminal Box CoverIMPORTANTAs it is possible that the insulation will deterio-rate, do not open the terminal box

Page 41 - F0416.EPS

IM 01E20D01-01E3-53. INSTALLATIONTable 3.3.1 Fitting DimensionsSizemm(inch)Code A B C D2.5(0.1)10(0.4)5(0.2)GURGUNGURGUNGURGUN22(0.87) 22(0.87) 22(0.

Page 42 - Flowtube

IM 01E20D01-01E3-63. INSTALLATION*: To be provided by userF0309a.EPS*Mounting baseGasketConnecting fittingUnion joint nut*PipingHorizontal mountingF0

Page 43 - 4.2.2 Cables

IM 01E20D01-01E3-73. INSTALLATION(3) Positioning the FlowmeterPass two through-bolts through the adjacent holes ofboth flanges and position the flowm

Page 44 - 4.2.3 Wiring Ports

IM 01E20D01-01E3-83. INSTALLATIONFigure 3.3.3 Mounting Procedure for Wafer Type (size: 25 (1.0), 32 (1.25), and 40 mm (1.5 in.))Table 3.3.4 Wafer

Page 45 - 4.2.4 Wiring Connections

IM 01E20D01-01E3-93. INSTALLATIONTable 3.3.5 Wafer Type Tightening Torque Values for PVC PipingJIS 10K, ANSI Class 150, and DIN PN10 JIS 20K, ANSI Cl

Page 46 - Te rminal

iCONTENTSIM 01E20D01-01E10th Edition: June 2012All Rights Reserved, Copyright © 2003, Yokogawa Electric CorporationContents1. INTRODUCTION ...

Page 47

IM 01E20D01-01E3-103. INSTALLATION3.3.3 Nominal Diameter 50 mm (2.0in.) to 300 mm (12.0 in.), WaferTypeIMPORTANTUse bolts and nuts in compliance with

Page 48 - F040218.EPS

IM 01E20D01-01E3-113. INSTALLATIONFigure 3.3.4 Mounting Procedure for Wafer Type (size: 50 mm (2 in.) to 300 mm (12 in.))Table 3.3.7 Wafer Type Ti

Page 49 - Flowtube)

IM 01E20D01-01E3-123. INSTALLATIONTable 3.3.8 Wafer Type Tightening Torque Values for PVC PipingTightening torque values for PFA lining typeGasket ty

Page 50 - 5. MAINTENANCE

IM 01E20D01-01E3-133. INSTALLATIONTable 3.3.9 Wafer Type Tightening Torque Values for Metal Piping and Permeable FluidsTightening torque values for P

Page 51 - Use Type Only)

IM 01E20D01-01E3-143. INSTALLATIONTable 3.3.12 Centering Device Identification (Replacement Models, PFA/Polyurethane Rubber lining)T0312-2.EPSANSI10K

Page 52 - F0506.EPS

IM 01E20D01-01E3-153. INSTALLATIONSize of Inner Diameter of Grounding ring andOuter Diameter for Effective Sealing :liningøB øAAXF FlowtubeGrounding

Page 53 - Electrode mounting screw

IM 01E20D01-01E3-163. INSTALLATION*Gasket (two units)*Piping-side flange*BoltFlowmeter-side flange*: These items must be provided by the user. Ch

Page 54 - Sanitary Types

IM 01E20D01-01E3-173. INSTALLATIONTable 3.3.15 Flange Type Tightening Torque Values for PVC PipingTightening torque values for PFA lining typeGasket

Page 55 - T0504.EPS

IM 01E20D01-01E3-183. INSTALLATIONTable 3.3.16 Flange Type Tightening Torque Values for Metal Piping and Permeable FluidsTightening torque values for

Page 56 - Flowmeter Only)

IM 01E20D01-01E3-193. INSTALLATION3.3.5 Nominal Diameter 500 mm (20in.) to 2600 mm (104 in.), FlangeTypeIMPORTANTUse bolts and nuts in compliance wit

Page 57 - (Integral Flowmeter

iiCONTENTSIM 01E20D01-01E5. MAINTENANCE ... 5-15.1 Ch

Page 58 - 5. MAINTENANCE

IM 01E20D01-01E3-203. INSTALLATIONTable 3.3.17 Installation Foundation Dimensions (Size500 mm (20 in.) to 1000 mm (40 in.)).LocationUnit: mm(approx.

Page 59 - T050601.EPS

IM 01E20D01-01E3-213. INSTALLATIONTable 3.3.19 Flange Type Tightening Torque Values for Material PipingRubber gasket, or the equivalent in hardnessJI

Page 60 - 5.8 Troubleshooting

IM 01E20D01-01E3-223. INSTALLATION3.3.6 Sanitary TypeThe sanitary type can be mounted to the piping using aclamp, a union, or a welded joint.NOTEThis

Page 61 - 5.8.2 Unstable Zero

IM 01E20D01-01E3-233. INSTALLATION(b) Union type(process connection codes: JDB, JKB, and JSB)1) Welding sleevePass the piping through a nut and then

Page 62

IM 01E20D01-01E3-243. INSTALLATIONCAUTION• In case of standard gasket (EPDM rubber),tighten the adapter mounting screw accordingto the torque values

Page 63 - 6. OUTLINE

IM 01E20D01-01E4-14. WIRING4. WIRING4.1 Wiring the IntegralFlowmeterThis section describes the wiring of the integral flowmeter.WARNINGThe wiring of

Page 64 - Functions

IM 01E20D01-01E4-24. WIRINGNOTE• For power cables, always use a crimp terminalwith an insulation cover.• Use crimp tools from the manufacturer of the

Page 65

IM 01E20D01-01E4-34. WIRING(3) Conduit WiringWhen wiring the conduits, pass the conduit through thewiring connection port, and utilize the waterproof

Page 66

IM 01E20D01-01E4-44. WIRING• Install an external switch or circuit breaker as ameans to turn the power off (capacitance; 15A,conforming to IEC947-1 a

Page 67

IM 01E20D01-01E4-54. WIRINGFor explosion proof type except TIIS, follow thedomestic electrical requirements as regulated ineach country.IMPORTANTWhen

Page 68 - Flowtube Material:

IM 01E20D01-01E1-11. INTRODUCTION1. INTRODUCTIONThis instrument has been adjusted at the factory beforeshipment.To ensure correct use of the instrume

Page 69 - T05-1.EPS

IM 01E20D01-01E4-64. WIRINGConnect the AXF integral flowmeter terminal toexternal instruments, giving attention to the followingpoints.For FOUNDATION

Page 70 - T23-2.EPS

IM 01E20D01-01E4-74. WIRING Status InputIMPORTANTStatus inputs are designed for use with no-voltage (dry) contacts. Be careful not to connectthe sta

Page 71 - ■ STANDARD PERFORMANCE

IM 01E20D01-01E4-84. WIRING4.2 Wiring the RemoteFlowtubeThis section describes the wiring of the remoteflowtube only. For information relating to the

Page 72

IM 01E20D01-01E4-94. WIRING4.2.2 Cables(1) Dedicated Signal Cable (AXFC)Outer jacket 10.5 (0.413")Tape Shield (C) Insulation Insulation Shields

Page 73 - ■ NORMAL OPERATING CONDITIONS

IM 01E20D01-01E4-104. WIRINGOn the converter side85 (3.35)EX1EX2EX1EX285 (3.35)On the flowtube side Unit : mm(approx. inch)F0419.EPSCrimp terminal Fi

Page 74

IM 01E20D01-01E4-114. WIRINGF0421.EPSGasketWasherTightening glandWhen working on conduit pipes or flexible pipes (PF1/2 only)CablePF1/2Figure 4.2.5 W

Page 75

IM 01E20D01-01E4-124. WIRINGABCEX1EX2Te rminalSymbolsDescriptionF042401.EPSFlow signal outputExcitation current inputFunctional grounding(Only for ex

Page 76

IM 01E20D01-01E4-134. WIRING(4) Wiring the Remote Flowtube (ExplosionProof Type) with ConvertersIMPORTANTIn case of TIIS Flameproof type, a remoteflo

Page 77

IM 01E20D01-01E4-144. WIRING(5) Wiring the Remote Flowtube (General-Purpose Use, Submersible Type, Size 500to 1000 mm (20 to 40 in.)) with Converters

Page 78 - TERMINAL WIRING

IM 01E20D01-01E4-154. WIRINGThe electromotive force of the magnetic flowmeter isminute and it is easy to be affected by noise. And alsothat reference

Page 79 - ■ MODEL AND SUFFIX CODE

IM 01E20D01-01E1-21. INTRODUCTIONIMPORTANTAn IMPORTANT sign denotes that attention isrequired to avoid damage to the instrument orsystem failure.NOTE

Page 80

IM 01E20D01-01E5-15. MAINTENANCE5. MAINTENANCEWARNING• Maintenance work must be carried out by thetrained personnel having knowledge of safetystandar

Page 81

IM 01E20D01-01E5-25. MAINTENANCE5.2 Removing, Cleaning,and Installing Re-placeable Electrodes(General-PurposeUse Type Only)5.2.1 Removing Replaceable

Page 82

IM 01E20D01-01E5-35. MAINTENANCE(6) Move aside the electrode lead wire and avoidingthe screw, insert end A of the tool to the electrodeand loosen the

Page 83 - Rubber Lining

IM 01E20D01-01E5-45. MAINTENANCE5.2.3 Installing Replaceable Elec-trodesNOTEIt is recommended to replace the O-ring whenreinstalling the replaceable

Page 84

IM 01E20D01-01E5-55. MAINTENANCENOTEAlways hold down the lead wire and terminal lugwhen adjusting the mounting screw.(5) Put the lead wire in the ele

Page 85 - T18-1.EPS

IM 01E20D01-01E5-65. MAINTENANCECAUTION• The lining of sanitary type uses fluorocarbonPFA. For the property of fluorocarbon PFA, it ispossible that t

Page 86 - Sanitary Type , PFA Lining

IM 01E20D01-01E5-75. MAINTENANCE5.4 Maintenance forConverter (IntegralFlowmeter Only)WARNING• Maintenance work must be carried out by thetrained pers

Page 87

IM 01E20D01-01E5-85. MAINTENANCEF0518-1.EPSClockwise 90°Display unit mounting screws (two screws)*1Figure 5.4.2 Changing the Display Unit Direction 9

Page 88 - OUNDATION

IM 01E20D01-01E5-95. MAINTENANCESwitch 1Low HighSwitch 2Enable ProtectF0520.EPS2 ← Burnout setting switch1 ← Write protect setting switchFigure 5.5.1

Page 89

IM 01E20D01-01E5-105. MAINTENANCECoil CircuitChecking is possible even if the pipe is filled withfluid. Test Terminals Test Voltage Specification50

Page 90

IM 01E20D01-01E1-31. INTRODUCTION• Care should be taken to prevent the build up ofdirt, dust or other substances on the displaypanel glass or data pl

Page 91

IM 01E20D01-01E5-115. MAINTENANCE5.8 TroubleshootingAlthough magnetic flowmeters rarely require maintenance, failures may occur when theinstrument is

Page 92

IM 01E20D01-01E5-125. MAINTENANCE5.8.2 Unstable ZeroSTARTCheck for the presence of valve leakage.• Confirm the flowmeter grounding. • Confirm whether

Page 93

IM 01E20D01-01E5-135. MAINTENANCE5.8.3 Disagreement Between Indication and Actual FlowNONONONOYESNONOYESYESYESNOYESYESNONOYESSet the parameters corre

Page 94

IM 01E20D01-01E6-16. OUTLINE STANDARD SPECIFICATIONSRefer to IM 01E20F02-01E for FOUNDATION Fieldbuscommunication type and IM 01E20F12-01E forPROFIB

Page 95

IM 01E20D01-01E6-26. OUTLINEFunctionsHow to Set Parameters (*2):The indicator’s LCD and three infra-red switches enableusers to set parameters withou

Page 96 - T26-6.EPS

IM 01E20D01-01E6-36. OUTLINE Flowtubes (Remote Flowtube/Integral Flowmeter)Size of AXF Flowtubes: AXF Standard (Lay length code 1)UseProcess Connect

Page 97 - ■ EXTERNAL DIMENSIONS

IM 01E20D01-01E6-46. OUTLINESize of AXF Flowtubes: AXF Standard (Lay length code 1) (continued)PFA15 (0.5), 25 (1.0), 32 (1.25), 40 (1.5) 50 (2.0), 6

Page 98

IM 01E20D01-01E6-56. OUTLINESize of AXF Flowtubes: Replacement model for earlier ADMAG or ADMAG AE (Lay length code 2)UseProcess ConnectionLiningRemo

Page 99

IM 01E20D01-01E6-66. OUTLINESubmersible Type: Non-tar epoxy coating (black)Flowtube Material:Size 2.5 mm (0.1 in.) to 15 mm (0.5 in.)Part NameMateria

Page 100 - 6. OUTLINE

IM 01E20D01-01E6-76. OUTLINESize 150 mm (6.0 in.) to 400 mm (16 in.)Part NameMaterialHousingFlangeProcess Connection code: B**Stainless steel-JIS SUS

Page 101

IM 01E20D01-01E1-41. INTRODUCTION1.4 ATEX DocumentationThis procedure is only applicable to the countries inEuropean Union.GBAll instruction manuals

Page 102 - Rubber /EPDM Rubber Lining

IM 01E20D01-01E6-86. OUTLINEGasket:CeramicsGasket Material (within Flowtube)Fluororesin with ceramic fillers(Valqua #7020)Gasket Material (within Fl

Page 103

IM 01E20D01-01E6-96. OUTLINENatural Soft Rubber, EPDM Rubber lining:Internal insertion typeCeramics lining: Integral typeSanitary Type: Internal inse

Page 104

IM 01E20D01-01E6-106. OUTLINEPolyurethane Rubber /Natural Soft Rubber /EPDM Rubber Lining:Size mm (in.)V  0.3 (1.0)1.0 mm/s0.3 ! V ! 10(1.0)

Page 105

IM 01E20D01-01E6-116. OUTLINECAUTION*1: When performing the Insulation Resistance Test or theWithstand Voltage Test, please obey the followingcaution

Page 106

IM 01E20D01-01E6-126. OUTLINECable Length and Liquid Conductivity (RemoteFlowtube):Cable lengthF03.EPSm (ft)200 (660)100 (330)50 (170)25 (85)0 (0)31

Page 107

IM 01E20D01-01E6-136. OUTLINEEnglish Units (Size: in., Flow rate: GPM)0 to Min. Span Flow Rate(0.33ft/s)0 to Max. Span Flow Rate(33ft/s)0to0.0078 GPM

Page 108

IM 01E20D01-01E6-146. OUTLINEGeneral-Purpose Use, Remote Flowtube (electrodestructure code 2: replaceable electrode)Pressure MPa (psi)2 (290)1 (

Page 109

IM 01E20D01-01E6-156. OUTLINENatural Soft Rubber LiningGeneral-Purpose Use and Submersible Type, RemoteFlowtube (electrode structure code 1: Non-repl

Page 110 - Grounding ring

IM 01E20D01-01E6-166. OUTLINE ACCESSORIESRemote Flowtube (size 2.5 to 1000 mm(0.1 to 40 in.)):Centering device (wafer type only): 1 pc.Hexagonal wre

Page 111

IM 01E20D01-01E6-176. OUTLINE MODEL AND SUFFIX CODEAXF STANDARD (Wafer Type)General-purpose Use/Submersible Type/Explosion proof Type, PFA/Polyureth

Page 112

IM 01E20D01-01E1-51. INTRODUCTIONLTLVPLESTSLOHBGROMCZSK

Page 113

IM 01E20D01-01E6-186. OUTLINE1 2 N*1: For a wafer type of 2.5 to 10 mm (0.1 to 0.4 in.), prepare 15 mm (0.5 in.) diameter nominal flanges on the pro

Page 114

IM 01E20D01-01E6-196. OUTLINEAXF STANDARD (Wafer /Union Joint Type)General-purpose Use/Explosion proof Type, Ceramics LiningUseConverter Output Sig

Page 115 - Size: inch

IM 01E20D01-01E6-206. OUTLINE*1: Even when DIN PN10 or 16 is required for a model of size 2.5 to 50 mm (0.1 to 2.0 in.), select PN40 (Process connect

Page 116 - Sanitary Type

IM 01E20D01-01E6-216. OUTLINEAXF STANDARD (Flange Type) Size 2.5 mm (0.1 in.) to 400 mm (16 in.)General-purpose Use/Submersible Type/Explosion proof

Page 117 - INSTRUMENT

IM 01E20D01-01E6-226. OUTLINE*1: For a flange type of 2.5 to 10 mm (0.1 to 0.4 in.), prepare 15 mm (0.5 in.) diameter nominal flanges on the process

Page 118 - T0804.EPS

IM 01E20D01-01E6-236. OUTLINEAXF STANDARD (Flange Type) Size 500 mm (20 in.) to 2600 mm (104 in.)General-purpose Use/Submersible Type, Polyurethane

Page 119

IM 01E20D01-01E6-246. OUTLINEAXF STANDARD (Clamp/Union/Butt Weld Connection)Sanitary Type , PFA LiningUseConverter Output Signal and CommunicationPo

Page 120 - T27-1.EPS

IM 01E20D01-01E6-256. OUTLINEREPLACEMENT MODEL FOR EARLIER ADMAG OR ADMAG AE (Wafer Type)General-purpose Use/Submersible Type/Explosion proof Type, P

Page 121 - F0802.EPS

IM 01E20D01-01E6-266. OUTLINE*1: For a wafer type of 2.5 to 10 mm (0.1 to 0.4 in.), prepare 15 mm (0.5 in.) diameter nominal flanges on the process p

Page 122 - 50 cm Max

IM 01E20D01-01E6-276. OUTLINEREPLACEMENT MODEL FOR EARLIER ADMAG OR ADMAG AE (Flange Type)General-purpose Use/Submersible Type/Explosion proof Type,

Page 123 - 8.4 IECEx

IM 01E20D01-01E2-12. HANDLING PRECAUTIONS2. HANDLING PRECAUTIONSThis instrument has been inspected carefully at thefactory before shipment. When the

Page 124 - 8.5 TIIS

IM 01E20D01-01E6-286. OUTLINE*1: Even when DIN PN10 is required for a 150 (6.0 in.)-mm model, select PN16 (Process connection code: CD2) because ther

Page 125 - F0809.EPS

IM 01E20D01-01E6-296. OUTLINE OPTIONAL SPECIFICATIONS FOR FLOWTUBES Table of Optional Specifications (Size 2.5 mm (0.1 in.) to 400 mm (16 in.)) “”

Page 126

IM 01E20D01-01E6-306. OUTLINE Table of Optional Specifications (Size 2.5 mm (0.1 in.) to 400 mm (16 in.)) (continued)SubmersibleSanitaryApplicable M

Page 127 - TIIS FLAMEPROOF EQUIPMENT

IM 01E20D01-01E6-316. OUTLINE Table of Optional Specifications (Size 2.5 mm (0.1 in.) to 400 mm (16 in.)) (continued)CodeSubmersibleSanitaryApplicab

Page 128 - Apparatus

IM 01E20D01-01E6-326. OUTLINE Table of Optional Specifications (Size 2.5 mm (0.1 in.) to 400 mm (16 in.)) (continued)Standard$90-degree rotation $18

Page 129 - 6. Maintenance of Flameproof

IM 01E20D01-01E6-336. OUTLINE Table of Optional Specifications (Size 500 mm (20 in.) to 2600 mm (104 in.))AXF***W-NSubmersibleAXF***G-NGeneralApplic

Page 130 - REVISION RECORD

IM 01E20D01-01E6-346. OUTLINE Table of Optional Specifications (Size 500 mm (20 in.) to 2600 mm (104 in.)) (continued)AXF***W-NSubmersibleAXF***G-NG

Page 131

IM 01E20D01-01E6-356. OUTLINE EXTERNAL DIMENSIONS AXF Standard, AXF002-AXF015, Wafer Type, PFA LiningUnit : mm (approx. inch)Remote FlowtubeIntegra

Page 132

IM 01E20D01-01E6-366. OUTLINE AXF Standard, AXF150-AXF300, Wafer Type, PFA /Polyurethane Rubber /Natural Soft Rubber /EPDMRubber LiningUnit : mm (ap

Page 133

IM 01E20D01-01E6-376. OUTLINE AXF Standard, AXF015, Wafer Type, Ceramics Lining*3: D, E, F, G; Integral Flowmeter, N, P; Remote Flowtube*3AX