<3. Operation>
3-18
IM 01C25T03-01E
• Example: Set the number of coodinates on the
line graph to 5.
ESCCLR
SET
T11:NUM OF POINT
5
FEED NO OK
SET
T11:NUM OF POINT
9
5
F0345.ai
Set 5.
Press the key twice to
enter the setting.
Press the (OK) key.
• Example: Set the first coordinates (X1, Y1) as
(12, 14) in %.
ESCCLR
SET
T23:Y1
10.00%
+ 014.00
CLR ESC
SET
T22:X1
10.00%
+ 012.00
F0346.ai
PARAM
T21:Y
0.00%
T22:X1
12.00%
T23:Y1
14.00%
PRNTDATA DIAG ESC
Set 12 for X1.
Press the key twice to
enter the setting.
Press the (OK) key.
Set 14 for Y1.
Press the key twice to
enter the setting.
Press the (OK) key.
• Example: Set the signal characterizer ENABLE.
ESC
SET
T10:S.C.ENABLE
ENABLE
FEED NO OK
SET
T10:S.C.ENABLE
INHIBIT
< INHIBIT>
< ENABLE >
F0347.ai
Use the or key
to select ENABLE.
Press the key twice to
activate the function.
Press the (OK) key.
(18) Process Alarm
(G10: P AL MODE, G11: P HI.AL VAL,
G12: P LO.AL.VAL)
The function is used to display the alarm codes
when the input pressure exceeds the specied
value within the calibration range. The same is
available for the input static pressure and the
capsule temperature on the pressure sensor.
Refer to table 4.1 Alarm Message Summary for the
specic alarm code to be generated.
• Example: Set alarm mode from OFF to HI.AL
DETECT.
ESC
SET
G10:P AL MODE
HI.AL DETECT
FEED NO ESC
SET
G10:P AL MODE
INHIBIT
< INHIBIT >
< HI.AL DETECT >
< LO.AL DETECT >
< HI/LO.AL DETECT >
Use the or key
to select HI. AL DETECT.
Press the key twice to
enter the setting.
Press the (OK) key.
Alarm code is generated when the
output goes beyond the value set
at G11: P HI. AL VAL.
F0348.ai
• Example: Set the higher alert value of 75 for
alarm generation.
CODE CAPS CLR ESC
SET
G11:P HI.AL VAL
75.0000 kPa
FEED NO OK
SET
G11:P HI.AL VAL
100.000 kPa
+ 75
Set 75.
Press the key twice to
enter the setting.
Press the (OK) key.
Then the alarm code “AL.35 P. HI”
is generated when the input
pressure goes beyond that value.
F0349.ai
(19) Status Output (option code AL)
This feature is used for a transistor output (open
collector) of an on/off signal according to the
status of high and low alarm limits, which are
user-congurable values as shown in (18) Process
Alarm. The status output can be assigned as
any combination of the high or low limits of the
input pressure, input static pressure, or capsule
temperature.
CAUTION
Execute DO testing by the parameter "K40:
DO test" whenever turning on the transmitter
or detecting the short interruption in order to
check that the alarm contact output is correctly
congured.
NOTE
No status output signal has been dened for a
CPU failure or hardware error. Use a 4-20 mA
signal to indicate a transmitters failure.