<5. Parameter Summary>
5-2
IM 01C25T03-01E
No. Parameter name Item
*1
R/W
Content Default value
Applicable
model
Upload
data
F P L
D AUX SET 1 Auxiliary setting data 1
D10 LOW CUT Low cut W 0.00 to 20.00% 10.00%
D11 LOW CUT MODE Low cut mode W LINEAR or ZERO LINEAR
D15 H/L SWAP Impulse piping accessing
direction
W NORMAL or REVERSE NORMAL
D16 H2O UNIT SEL H2O unit select W @4degC or @20degC
(68.0F)
@4degC
D20 OUT LIMIT (L) Low side output limiter W -2.50 to 110.00% -2.50%
D21 OUT LIMIT (H) High side output limiter W -2.50 to 110.00% 110%
D22 REV OUTPUT Output reversal W NORMAL or REVERSE NORMAL
D25 BURNOUT CPU error R HIGH or LOW
D26 ERROR OUT Hardware error W BURNOUT DIR or HOLD BURNOUT DIR
D30 SP UNIT Static pressure unit W See C20 MPa
D31 SP A/G SLCT Gauge/Abs select for static
pressure
W GAUGE or ABSOLUTE ABSOLUTE
D32 ATM. PRESS Coefcient for given gauge
pressure
W Unit specied in D30 0.10133 MPa
D33 SP LRV Lower limit of static pressure W -32000 to 32000 within
measurement range
0.0 MPa
D34 SP URV Upper limit of static pressure*
2
W -32000 to 32000 within
measurement range
D35 SP POINT Decimal place of static
pressure
W 0 to 4 1
D36 SP DAMPING Damping time constant of SP W 0.00 to 100.00 seconds 2.00 seconds
D37 SP SELECT H/L select for static pressure W HIGH or LOW HIGH
D40 TEMP UNIT Temperature setting unit W degC, degF, or K degC
D50 QUICK RESP Quick response W OFF or ON (enable 0.00 to
0.50 seconds at C30)
OFF
D55 WRT PROTECT Write protect indicator R NO or YES NO
D56 WRT ENABLE Write protect release W 8 alphanumeric characters None
D57 NEW PASSWORD User set password for write
protect
W 8 alphanumeric characters None
D58 SOFTWR SEAL Software seal R BREAK or KEEP KEEP
D60 SELF CHECK Self-diagnostics R See A60
E AUX SET 2 Auxiliary setting data 2
E10 T. ZERO CMP Temperature compensation
mode
W OFF or ON OFF
E11 TEMP ZERO Zero shift compensation W -99.999 to 99.999%/degC 0.000%/degC
E30 BI DIRE MODE Bidirectional mode W OFF or ON OFF
E50 DO SELECT Contact output select W INHIBIT, PRES, SP, TEMP,
PRES/SP, PRES/TEMP, SP/
TEMP, or PRES/SP/TEMP
INHIBIT
E51 DO SIG. TYPE Signal type select W OFF WHEN ALARM or ON
WHEN ALARM
ON WHEN
ALARM
E52 D OUTPUT Contact output R OFF or ON OFF
E60 SELF CHECK Self-diagnostics R See A60
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.