Setting the Flow Rate Measurement Channel, the Input Range, the Alarm, and Tag
FX
Flowmeter Channel 2
4 - 20 mA
Convert to 1-5 V with a shunt resistor
Setup Item Description Number in the Figure
Channel Use channel 2. 1
Tag FI-002 2
Input signal 1-5V 3
Input range 0.0 to 500.0 L/H 4
Alarm condition Output an alarm if the measured value is
less than or equal to 120.0 L/H.
Output destination: Relay contact (I03)
5
(1) Input Range and Alarm
Press MENU (switch to the setting mode).
Select the Menu tab > Meas channel > Range, Alarm.
1
5
4
3
(2) Tag
Select the Menu tab > Meas channel > Tag, Memory, Delay.
2
Operation complete.
For more details of the setting alarm, see Section 3.7 “Setting Alarms on Channels”, in
the FX1000 User’s Manual, IM 04L21B01-01EN.