User’sManualFX1000Communication Interface(/C2, /C3, /C7)2nd EditionIM 04L21B01-17EN
1-2IM 04L21B01-17ENModbus Server• A Modbus client device can carry out the following operations on the FX that is operating as a Modbus server device
3-183.4 Setting CommandsIM 04L21B01-17ENST Sets a tagSyntax STp1,p2<terminator>p1 Measurement or computation channel numberp2 Tag (up to 1
3-19IM 04L21B01-17ENCommands123456AppIndexTF Sets a data file nameSyntax TFp1,p2,p3<terminator>p1 Fixed to 1p2 ConfigurationBATCH File nam
3-203.4 Setting CommandsIM 04L21B01-17ENSE Sets the line width and the number of grid sections to use on the trend graphSyntax SEp1,p2<terminat
3-21IM 04L21B01-17ENCommands123456AppIndexTG Sets a color scale bandSyntax TGp1,p2,p3,p4,p5,p6,p7<terminator>p1 Measurement or computation c
3-223.4 Setting CommandsIM 04L21B01-17ENTR Sets the automatic monitor return functionSyntax TRp1<terminator>p1 Automatic return time limit
3-23IM 04L21B01-17ENCommands123456AppIndexTU Sets an event actionSyntax TUp1,p2,p3,p4,p5,p6,p7<terminator>p1 Logic number (1 to 40)p2 Event
3-243.4 Setting CommandsIM 04L21B01-17ENSK Sets a computation constant (/M1, /PM1, and /PWR1 options)Syntax SKp1,p2<terminator>p1 Computati
3-25IM 04L21B01-17ENCommands123456AppIndexTX Sets the ancillary operation of the start key (/M1,/PM1, and /PWR1 options)Syntax TXp1<terminator&g
3-26IM 04L21B01-17ENDescription • Use parameter p2 to set the VT ratio. VT ratio (p2): 10 to 60000 Set this value using an integer without a decima
3-27IM 04L21B01-17ENCommands123456AppIndexSM Sets the custom menuSetting the main menuSyntax SMp1,p2,p3,p4,p5,p6,p7,p8,p9<terminator>p1 Type
1-3IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexSetting/Measurement Server• This function can be used to set almost all of
3-28IM 04L21B01-17EN When p2 is set to INFORMATION, select from the items belowALARM Alarm summaryMESSAGE Message summaryMEMORY Memory summary
3-29IM 04L21B01-17ENCommands123456AppIndexSetting the function menup1 Type (FUNC)p2 and additional parameters Menu item to display The FX displ
3-30IM 04L21B01-17EN3.5 Control CommandsBT Sets a batch nameSyntax BTp1,p2,p3<terminator>p1 Fixed to 1p2 Batch number (up to 32 characters
3-31IM 04L21B01-17ENCommands123456AppIndexEV Executes manual sample, generates a manual trigger, takes a snapshot, or causes a timeoutSyntax EVp1&l
3-32IM 04L21B01-17ENExample Switch the FX to basic setting mode.DS1Description • You cannot set p1 to 1 when the FX is recording (memory sampling) o
3-33IM 04L21B01-17ENCommands123456AppIndexCU Recovers Modbus manuallySyntax CUp1<terminator>p1 Communication type0 Modbus client (Ethernet)
3-34IM 04L21B01-17EN3.6 Basic Setting CommandsWU Sets the environmentSetups GENERAL,BATCH,DISPLAY,MESSAGE,INPUT,ALARM,SECURITY,MEDIA,MATH,
3-35IM 04L21B01-17ENCommands123456AppIndexComputation settingsSyntax WUp1,p2,p3,p4<terminator>p1 Setting type (MATH)p2 Display on error+OVER
3-36IM 04L21B01-17ENDetailed POP3 settingsSyntax WUp1,p2,p3<terminator>p1 Setting type (POP3)p2 Delay after accessing POP3 until transmissio
3-37IM 04L21B01-17ENCommands123456AppIndexXV Sets the scan interval and A/D integration timeSyntax XVp1,p2,p3,p4<terminator>p1 Fixed to 1p2
1-4IM 04L21B01-17ENFTP Server• You can use a PC to access the FX via FTP. You can perform operations such as retrieving directory and file lists from
3-38IM 04L21B01-17ENRN Sets basic loginSyntax RNp1,p2<terminator>p1 Auto logout (OFF, 1MIN, 2MIN, 5MIN, 10MIN)p2 Operation without LoginOFF
3-39IM 04L21B01-17ENCommands123456AppIndexRM Sets a report channel (/M1, /PM1, and /PWR1 options)When you are not using report channelsSyntax RMp1,
3-40IM 04L21B01-17ENYD Sets network parameters (/C7 option)When you are not retrieving network parameters automaticallySyntax YDp1<terminator>
3-41IM 04L21B01-17ENCommands123456AppIndexYQ Sets the communication timeout (/C7 option)When you are not using a timeoutSyntax YQp1<terminator&g
3-42IM 04L21B01-17ENWhen you want to send system notificationsSyntax YU p1,p2,p3,p4,p5,p6,p7<terminator>p1 Information to send (SYSTEM)p2 Re
3-43IM 04L21B01-17ENCommands123456AppIndexYP Sets basic Modbus client settings (/C7 option)Syntax YPp1,p2<terminator>p1 Read cycle (1S, 2S,
3-44IM 04L21B01-17ENWC Sets the SNTP operation that is performed when memory start is executed (/C7 option)Syntax WCp1<terminator>p1 Time ad
3-45IM 04L21B01-17ENCommands123456AppIndexWhen you are reading communication input data from another deviceSyntax YM p1,p2,p3,p4,p5,p6,p7<termina
3-46IM 04L21B01-17ENQA Sets the number of mantissa digits to display (/LG1 option)Syntax QAp1<terminator>p1 Number of digits to display (2,
3-47IM 04L21B01-17ENCommands123456AppIndex3.7 Output Commands (Control)BO Sets the byte output orderSyntax BOp1<terminator>p1 Byte order0
1-5IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexFTP ClientAutomatic transferring of files• The display data, event data, re
3-48IM 04L21B01-17EN3.8 Output Commands (Setting, measured, and computed data output)FC Outputs screen image dataSyntax FCp1<terminator>p1
3-49IM 04L21B01-17ENCommands123456AppIndexFF Outputs FIFO dataSyntax FFp1,p2,p3,p4<terminator>p1 Action typeGET Output starting with the ne
3-50IM 04L21B01-17ENFU Outputs user levelsSyntax FUp1<terminator>p1 User information output0 Information about the users who are currently
3-51IM 04L21B01-17ENCommands123456AppIndexMO Manages and outputs the data that has been written to internal memorySyntax MOp1,p2,p3<terminator&g
3-52IM 04L21B01-17EN3.10 Output Commands (Special response commands)*I Outputs instrument informationSyntax*I<terminator>Description Upon rec
3-53IM 04L21B01-17ENCommands123456AppIndexeth Outputs Ethernet statisticsSyntax eth<terminator>ExampleethEA11/06/0912:34:56EthernetStatistic
3-54IM 04L21B01-17EN3.12 Instrument Information Output Commands3.12 Instrument Information Output Commands (Available when using the instrument info
4-1IM 04L21B01-17ENResponses123456AppIndex4.1 Response SyntaxThe following table shows the types of responses for various commands described in the p
4-2IM 04L21B01-17EN• SyntaxE2_ee:nnnCRLF (When there is only one error)E2_ee:nnn,ee:nnn,···,ee:nnnCRLF (When there are multiple errors)ee
4-3IM 04L21B01-17ENResponses123456AppIndexFlagBit Name (Abbreviation) Flag Meaning of the Flag 0 17 BO MSB LSB Output byte o
1-6IM 04L21B01-17ENLogin• This function can be used only when using the setting/measurement server, maintenance/test server, and the FTP server funct
4-4IM 04L21B01-17ENCalculating the Sum ValueIf you set the parameter of the CS command to 1 (enabled), the checksum value is output only during serial
4-5IM 04L21B01-17ENResponses123456AppIndex if((csum=(csum&0xffff)+((csum>>16)&0xffff))0xffff) /* Add the ove
4-6IM 04L21B01-17EN4.2 Output Format of Text DataThe following types of text data are available. The format for each type is described in this sectio
4-7IM 04L21B01-17ENResponses123456AppIndex• ExampleEASR001,VOLT,20mV,0,20SR002,VOLT,20mV,0,20···················ENDecimal Place/Unit Information• Th
4-8IM 04L21B01-17ENMeasured and Computed Data• The FD command is used to output the data.• You can use the CB command to specify whether to output t
4-9IM 04L21B01-17ENResponses123456AppIndexddddd Mantissa (00000 to 99999, 5 digits) • Eight digits for computed data. • For abnormal dat
4-10IM 04L21B01-17ENCommunication Log• The FL command is used to output the data.• A log of setting/basic setting/output commands and responses is o
4-11IM 04L21B01-17ENResponses123456AppIndex Transmission(dddbyte): Data output (where ddd is the number of data values)(Login): Login(Logout)
4-12IM 04L21B01-17ENFTP Client Log• The FL command is used to output the data.• The FTP client log is output. Up to 50 file transfer logs are retain
4-13IM 04L21B01-17ENResponses123456AppIndexOperation Error Log• The FL command is used to output the data.• The operation error log is output. Up to
1-7IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexWeb ServerMicrosoft Internet Explorer can be used to display the FX screen o
4-14IM 04L21B01-17ENLogin Log• The FL command is used to output the data.• A log of users that have logged in and logged out is output. Up to 50 log
4-15IM 04L21B01-17ENResponses123456AppIndexWeb Operation Log• The FL command is used to output the data.• The log of operations on the Web screen is
4-16IM 04L21B01-17EN• ExampleEA11/02/1112:20:00SCREEN275TREND0111/02/1112:21:00SCREENBAR11/02/1112:30:00KEYUP11/02/1112:31:00
4-17IM 04L21B01-17ENResponses123456AppIndexE-mail Log• The FL command is used to output the data.• The e-mail transmission log is output. Up to 50 o
4-18IM 04L21B01-17ENSNTP Log• The FL command is used to output the data.• The SNTP log is output. Up to 50 accesses to the SNTP server are retained.
4-19IM 04L21B01-17ENResponses123456AppIndexDHCP Log• The FL command is used to output the data.• The DHCP log is output. Up to 50 accesses to the DH
4-20IM 04L21B01-17ENThe table below shows the contents of the log during erroneous operation.Error Number Detail Code Description295 REJECT Addres
4-21IM 04L21B01-17ENResponses123456AppIndexModbus Communication Log• The FL command is used to output the data.• The Modbus communication log is out
4-22IM 04L21B01-17ENAlarm Summary• The FL command is used to output the data.• The alarm summary is output. Up to 1000 alarm events are retained. Al
4-23IM 04L21B01-17ENResponses123456AppIndexMessage Summary• The FL command is used to output the data.• The message summary is output. Up to 100 mes
1-8IM 04L21B01-17ENE-mail TransmissionTransmitting e-mail messagesThe available types of e-mails are listed below. E-mail can be automatically transmi
4-24IM 04L21B01-17ENStatus Information• The IS command is used to output the data. The output format varies between IS0 and IS1.• The operation stat
4-25IM 04L21B01-17ENResponses123456AppIndexEthernet Information• The FA command is used to output the data.• SyntaxEACRLFIP_Address______:xxx.xxx.x
4-26IM 04L21B01-17ENFile List• The ME command is used to output the data.• The file sizes and a list of files from the specified directory in the ex
4-27IM 04L21B01-17ENResponses123456AppIndexCheck DiskThe ME command is used to output the free space on the storage medium.• Syntax EACRLFzzz···_Kby
4-28IM 04L21B01-17ENManual Sampled/Report Data SizeThis is generated by the MO command.• SyntaxEACRLFzzz···CRLFENCRLFzzz···Thedatasize(10digits
4-29IM 04L21B01-17ENResponses123456AppIndex4.3 Output Format of Binary DataThis section describes the output format of the binary data.For informatio
4-30IM 04L21B01-17ENMeasured/Computed Data and FIFO Data• The FD command is used to output the measured/computed data.• The FF command is used to ou
4-31IM 04L21B01-17ENResponses123456AppIndex• Flag The meaning of the each flag is given in the table below. The flags are valid during FIFO data out
4-32IM 04L21B01-17ENConfigured Channel Information Data• The FE5 command is used to output the data.• The ID number of the output format is 25.• Yo
4-33IM 04L21B01-17ENResponses123456AppIndexConfigured Alarm Information Data• The FE6 command is used to output the data.• The ID number of the outp
1-9IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexSNTP Server/ClientThe client function retrieves time information from a spec
4-34IM 04L21B01-17EN4.4 Output Format of Instrument InformationThis section describes the instrument information output format of the instrument info
5-1IM 04L21B01-17ENStatus Reports123456AppIndex5.1 Status Information and FilterThe following figure illustrates the status information and filter on
5-2IM 04L21B01-17EN5.2 Bit Structure of the Status InformationThe following four groups of status information are output in response to a status info
5-3IM 04L21B01-17ENStatus Reports123456AppIndexStatus Information 4Bit Name Description0 A/D conversion complete Set to 1 when the A/D conversion of
Blank Page
6-1IM 04L21B01-17ENSpecifications123456AppIndex6.1 Ethernet Interface SpecificationsBasic SpecificationsElectrical and mechanical specifications: Co
6-2IM 04L21B01-17EN6.2 Serial Interface SpecificationsRS-232 SpecificationsConnector type: D-Sub 9-pin plugElectrical and mechanical specifications:
6-3IM 04L21B01-17ENSpecifications123456AppIndex6.3 Modbus Protocol SpecificationsModbus Client FunctionBasic Operation• The FX, as a Modbus client d
6-4IM 04L21B01-17ENCommandCommand type: R-M, W, W-MNumber of commands: Set up to 16 commandsData type: See the table below.Symbol Descr
6-5IM 04L21B01-17ENSpecifications123456AppIndex • Writing the Computed Values of the Computation Channels• The computation function is an option (/M
1-10IM 04L21B01-17EN1.2 Flow of Operation When Using the Ethernet InterfaceFollow the flowchart below to set the Ethernet communications.Set the host
6-6IM 04L21B01-17ENModbus Server FunctionModbus Server SpecificationsCommunicate via ModbusTCPCommunication media: Ethernet 10Base-TPort: 502/tcp (d
6-7IM 04L21B01-17ENSpecifications123456AppIndexInput Register (shared with the Modbus slave function)• Common Items• The client device can only read
6-8IM 04L21B01-17ENInput Register Data Data Type306001 List of alarms of measurement channels 001 to 004 Bit string | |306003 List
6-9IM 04L21B01-17ENSpecifications123456AppIndexHold Register (shared with the Modbus slave function)• Common Items• The client device can read and w
6-10IM 04L21B01-17ENList of RegistersRegister Description Supplementary Information Type Access Simultaneous AccessWrite Read406061 Internal switch 1
6-11IM 04L21B01-17ENSpecifications123456AppIndexRegister Description Supplementary Information Type Access Simultaneous AccessWrite Read410611 Free me
6-12IM 04L21B01-17ENHow to UseItem DescriptionData type STRnn Registers in which ASCII codes are entered starting with the specified register. It is t
6-13IM 04L21B01-17ENSpecifications123456AppIndexModbus Error Response (Common to Modbus server and Modbus slave)The FX returns the following error cod
6-14IM 04L21B01-17ENModbus Master FunctionBasic Operations• The FX, as a Modbus master device, communicates with Modbus slaves periodically by sendin
6-15IM 04L21B01-17ENSpecifications123456AppIndexModbus Slave FunctionSerial Communication Specifications: Same as the Modbus Master FunctionSlave addr
1-11IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.3 Connecting the FXConnecting to the PortConnectorConnect an Ethernet ca
Blank Page
App-1IM 04L21B01-17ENAppendix123456AppIndexAppendix 1 Data Dropout during Modbus CommunicationData Dropout during Modbus ClientIf the response to the
App-2IM 04L21B01-17ENData Dropout during Modbus MasterIf the response to the previous command is not complete when the FX attempts to issue a command
App-3IM 04L21B01-17ENAppendix123456AppIndexAppendix 2 Login ProcedureYou log into the FX from your PC to use the functionality of the setting/measure
App-4IM 04L21B01-17ENWhen Not Using the Login Function of the FXLogin as “admin” or “user.”• The user name “admin” can be used to login to the FX as
App-5IM 04L21B01-17ENAppendix123456AppIndexAppendix 3 ASCII Character Codes 0123456789ABCDEF0LFCR1ESC2SP#%&()*+-./30123456789:4@ABCDEFGHIJKLMNO5P
App-6IM 04L21B01-17ENKorean CharactersThe Korean characters that you can enter are shown below.Other characters that you can enter are the same as whe
App-7IM 04L21B01-17ENAppendix123456AppIndexAppendix 4 Output Flow of the File or the File List on the External Storage Medium and Internal MemoryExam
App-8IM 04L21B01-17ENExample in Which the File List Is Output 10 Files at a TimeThe figure below shows the flow in which the file list in the DATA0 di
App-9IM 04L21B01-17ENAppendix123456AppIndexAppendix 5 Flow Chart of the FIFO Data OutputOverview of the FIFO BufferThe FX has a dedicated internal me
1-12IM 04L21B01-17ENSetting the IP Address Host Information and DNS◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to bas
Blank Page
Index-1IM 04L21B01-17ENIndexIndex123456AppIndexNumerics1-5V voltage ... 3-1010Base-
Index-2IM 04L21B01-17ENST ... 3-18SV ...
Index-3IM 04L21B01-17ENIndex123456AppIndexfinal character ... 3-2first/last (client
Index-4IM 04L21B01-17ENPpage type ... 1-28parameter ...
Index-5IM 04L21B01-17ENIndex123456AppIndexXXON-RS ... 2-6XON-XON ...
Blank Page
1-13IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexWhen using a fixed IP address• DHCP Set DHCP to Not.• IP address Set th
1-14IM 04L21B01-17ENRequesting/Releasing Network Information from DHCPYou can manually request or release network information such as the IP address.
1-15IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexReleasing Network Information1. Display the network information screen.◊
1-16IM 04L21B01-17ENSetting the Communication Status◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic setting mode
1-17IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.4 Sending E-mail MessagesSettings for Sending E-mailSet the server confi
1-18IM 04L21B01-17ENBasic SettingsSet the SMTP server and mail address.• SMTP server name Enter the host name or IP address of the SMTP server.• Po
1-19IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex• Include source URL Select On to attach the source URL. Attach the URL w
1-20IM 04L21B01-17ENConfiguring the POP3 Server ConnectionSpecify how the FX operates when it connects to a POP server.◊ Press MENU (to switch to sett
1-21IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexE-mail FormatThe formats of alarm e-mails, scheduled e-mails, system e-mail
iIM 04L21B01-17ENThank you for purchasing the FX1000 (hereafter referred to as “FX”).This User’s Manual contains information about the Ethernet/serial
1-22IM 04L21B01-17ENScheduled E-mail Format• SubjectSubject:Periodic_Data• Syntaxheader1CRLFheader2CRLFCRLFPeriodic_data.CRLF<Host_name>CRLFho
1-23IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexSystem Mail (Power Failure) Format• SubjectSubject:System_warning• Synta
1-24IM 04L21B01-17ENSystem Mail (Error) Format• SubjectSubject:System_warning• Syntaxheader1CRLFheader2CRLFCRLFError.CRLF<Host_name>CRLFhostCR
1-25IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexReport Mail Format• SubjectSubject:Report_data• Syntaxheader1CRLFheader2C
1-26IM 04L21B01-17ENTest E-mail Format• SubjectSubject:Test• SyntaxTest_mail.CRLF<Host_name>CRLFhostCRLFCRLF<Time>CRLFmo/dd_hh:mi:ssCR
1-27IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.5 Monitoring the FX on a PC BrowserSetting the Web Server FunctionFrom t
1-28IM 04L21B01-17ENPage Type• Monitor Configure the monitor page. You can carry out the following operations on the monitor page.• Display the ala
1-29IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexMonitoring with a BrowserSetting the URLSet the URL appropriately according
1-30IM 04L21B01-17ENContents of the Monitor PageNote If the FX is in setting mode or basic setting mode, you cannot display the monitor page or the o
1-31IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexContents of the Operator PageSelect the trend screenDirectly select the gro
iiIM 04L21B01-17ENConventions Used in This Manual• UnitK Denotes 1024. Example: 768 KB (file size)k Denotes 1000.• MarkingsThe following markings
1-32IM 04L21B01-17ENAlarm SummaryClick Alarm Summary to display the alarm summary. Click Refresh to update the data.• You can display information for
1-33IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexWriting Messages (Operator page only)You can assign a text string to one of
1-34IM 04L21B01-17EN1.6 Accessing the Measurement Data File on the FX from a PCYou can access data files stored on the external storage medium and da
1-35IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexWhen Not Using the Login FunctionYou can connect to the server using the us
1-36IM 04L21B01-17EN1.7 Transferring Measurement Data Files and Other Files from the FXThe display and event data files, report data files, and snaps
1-37IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexSetting the FTP Connection DestinationConsult your network administrator wh
1-38IM 04L21B01-17ENTesting the FTP TransferYou can test whether a test file can be transferred from the FX to an FTP server.◊ Press FUNC and select
1-39IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.8 Synchronizing the TimeThe FX time can be synchronized to the time on a
1-40IM 04L21B01-17ENSetting the SNTP ServerCarry out the steps below to run the FX as an SNTP server.◊ Press MENU (to switch to setting mode), hold d
1-41IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.9 Using the Modbus Server FunctionThe FX is used as a Modbus server.For
iiiIM 04L21B01-17ENNames and Uses of Parts and the Setup Procedures Using the Operation KeysFront PanelSoft keysPress these keys to select the menu di
1-42IM 04L21B01-17ENPort NumberThe default value is 502. To change the setting,◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to s
1-43IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.10 Using Modbus to Read Data From and Write Data to Other DevicesThe FX
1-44IM 04L21B01-17EN• Unit Select Auto if the unit number of the destination server is not required; Otherwise, select Fixed. If you select Fixed, t
1-45IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexExamples of Setting CommandsThe following are examples of setting commands
1-46IM 04L21B01-17ENWriting Measured Values to the Server• Example Write the measured value (16-bit signed integer) from channel 001 to register 40
1-47IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexChecking the Modbus Operating StatusDisplaying the Modbus Operating Status◊
1-48IM 04L21B01-17ENResuming Command TransmissionYou can use the front panel keys to resume command transmission to a server device to which communica
1-49IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.11 Usage Example of the Modbus FunctionExplains the setting example for
1-50IM 04L21B01-17ENSettings on the FX1000 Server (Modbus Server)Setting the Modbus Server Function◊ Press MENU (to switch to setting mode), hold dow
1-51IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexSetting the FX1000 Client (Modbus Client)Assumes the settings other than th
ivIM 04L21B01-17ENContentsNames and Uses of Parts and the Setup Procedures Using the Operation Keys ... iiiChapter 1 Using th
1-52IM 04L21B01-17ENSetting the Computation Channel◊ Press MENU (to switch to setting mode), and select the Menu tab > Math channel > Expressio
1-53IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndexStarting the Computation (FX1000 Client)◊ Press FUNC and select Math start
1-54IM 04L21B01-17EN1.12 Using the Setting/Measurement ServerThis section explains how to use the setting/measurement server. You can use this functi
1-55IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.13 Using the Maintenance/Test ServerWhen Not Using the Login FunctionAcc
Blank Page
2-1IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex2.1 What You Can Do with the FX1000You can use an RS-2
2-2IM 04L21B01-17ENModbus Slave• A Modbus master device can carry out the following operations on the FX that is operating as a Modbus slave device.•
2-3IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex2.2 Flow of Operation When Using the Serial InterfaceT
2-4IM 04L21B01-17EN2.3 Connecting the FXConnecting the cableConnect a cable to the serial port on the FX rear panel.RS-232 Connection ProcedureConnec
2-5IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex• Connection example SD RD RS CS SG SD RD RS SG •
IM 04L21B01-17ENv123456AppIndexChapter 5 Status Reports5.1 Status Information and Filter ...
2-6IM 04L21B01-17EN• XON-XON• Data transmission control Software handshaking is performed between the FX and the PC. When an “X-OFF” code is receiv
2-7IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndexRS-422A/485 Connection ProcedureTerminal arrangement an
2-8IM 04L21B01-17ENConnection example to the host deviceYou can connect the FX to a host device that has an RS-232, RS-422A, or RS-485 port.Use a conv
2-9IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndexNote• The method used to eliminate noise varies depend
2-10IM 04L21B01-17EN2.4 Setting the Serial Communication◊ Press MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic setting
2-11IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex2.5 Using the Modbus Slave FunctionThe FX is used as
2-12IM 04L21B01-17EN2.6 Using Modbus to Read Data From and Write Data to Other DevicesThe FX is used as a Modbus master.For the Modbus specifications
2-13IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex• First/Last (FX channel numbers) Enter the first an
2-14IM 04L21B01-17EN• Communication conditions The read cycle, Inter-block delay, Time out, Auto recovery, and Retrials settings are displayed.• Co
2-15IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndex2.7 Usage Example of the Modbus FunctionExplains the
Blank Page
2-16IM 04L21B01-17ENSettings on the FX1000 Slave (Modbus Slave)Setting the Modbus Slave Function◊ Press MENU (to switch to setting mode), hold down F
2-17IM 04L21B01-17ENUsing the Serial Communication Interface (/C2 and /C3 Options)123456AppIndexSetting the FX1000 Master (Modbus Master)Assumes the s
2-18IM 04L21B01-17EN2.8 Using the Setting and Measurement FunctionThis section explains the setting and measurement function. You can use this functi
3-1IM 04L21B01-17ENCommands123456AppIndex3.1 Command SyntaxCommand SyntaxThe syntax of the FX’s setting, basic setting, and output commands (see sect
3-2IM 04L21B01-17ENQuery• A question mark is used to specify a query.• By placing a query after a command or parameter, you can query the correspond
3-3IM 04L21B01-17ENCommands123456AppIndexResponseThe FX returns a response (affirmative or negative acknowledgment) to each command that is delimited
3-4IM 04L21B01-17EN3.2 List of CommandsFX Execution ModesThe FX has two execution modes. If you attempt to execute a command in an execution mode tha
3-5IM 04L21B01-17ENCommands123456AppIndexCommand NameFunction Execution Mode Administrator User PageTQ Sets a timer Operation mode Yes No 3-22TK Sets
3-6IM 04L21B01-17ENControl CommandsCommand NameFunction Execution Mode Administrator User PageBT Sets a batch name Operation mode Yes No 3-30BU Sets a
3-7IM 04L21B01-17ENCommands123456AppIndexBasic Setting Commands• To apply settings that you have changed using the basic setting commands, you need t
1-1IM 04L21B01-17ENUsing the Ethernet Interface (/C7 Option)123456AppIndex1.1 What You Can Do with the FX1000This section gives an overview of the co
3-8IM 04L21B01-17ENCommand NameFunction Execution Mode Administrator User PageYM Sets a transmit command of the Modbus master function (/C2 and /C3 op
3-9IM 04L21B01-17ENCommands123456AppIndex3.3 Setup ParametersExample of Entering Measuring Range ParametersWhen you enter the span upper and lower li
3-10IM 04L21B01-17ENList of Measuring Range ParametersThe table below shows the relationship between the input types and the range parameters. For det
3-11IM 04L21B01-17ENCommands123456AppIndexList of Notations Such as Channel Numbers and Valid RangesType Notation and Valid RangeNotesMeasurement chan
3-123.4 Setting CommandsIM 04L21B01-17EN3.4 Setting CommandsSR Sets an input range You cannot use this command to configure settings while recordi
3-13IM 04L21B01-17ENCommands123456AppIndexWhen Setting Channels to Square Root ComputationSyntax SRp1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11<terminator&
3-143.4 Setting CommandsIM 04L21B01-17EN• When Setting Channels to Log Linear Input/Pseudo log inputSyntax SRp1,p2,p3,p4,p5,p6,p7,p8,p9,p10<te
3-15IM 04L21B01-17ENCommands123456AppIndexSA Sets an alarmWhen Not Using AlarmsSyntax SAp1,p2,p3<terminator>p1 Measurement or computation ch
3-163.4 Setting CommandsIM 04L21B01-17EN• If p6 is set to OFF, the relay number (p7) is a Don’t care value in setting commands. In queries, this par
3-17IM 04L21B01-17ENCommands123456AppIndexTE Sets sampling conditions for event dataSyntax TEp1,p2,p3,p4,p5,p6<terminator>p1 1p2 Sample rat