User’sManualDPharpPROFIBUS PA Communication Type(EJXA, EJAE)IM 01C25T04-01ENIM 01C25T04-01EN1st Edition
<2. Handling Cautions>2-2IM 01C25T04-01EN2.1.2 CSA Certicationa. CSA Explosionproof TypeCaution for CSA explosionproof type.Note 1. The
<2. Handling Cautions>2-3IM 01C25T04-01EN2.1.3 ATEX Certication(1) Technical Dataa. ATEX Flameproof TypeCaution for ATEX ameproof typ
<2. Handling Cautions>2-4IM 01C25T04-01ENb. ATEX Intrinsically Safe Ex iaCaution for ATEX Intrinsically safe type.Note 1. EJX/EJA-E serie
<2. Handling Cautions>2-5IM 01C25T04-01ENNote 6. Installation InstructionsNon-Hazardous LocationHazardous LocationF0202.aiTerminatorSafety
<2. Handling Cautions>2-6IM 01C25T04-01ENNote 4. Specic Conditions of UseWARNING • Electrostatic charge may cause an explosion hazard. A
<2. Handling Cautions>2-7IM 01C25T04-01ENSTYLE: Style code.SUFFIX: Specied sufx code.SUPPLY: Supply voltage.OUTPUT: Output signal.MWP: Ma
<3. About PROFIBUS PA>3-1IM 01C25T04-01EN3. About PROFIBUS PA3.1 OutlinePROFIBUS PA is a widely used bi-directional digital communication
<4. Getting Started>4-1IM 01C25T04-01EN4. Getting StartedPROFIBUS PA is fully dependent upon digital communication protocol and differs in
<4. Getting Started>4-2IM 01C25T04-01EN4.2 Bus Power ONTurn on the power of the host and the bus.For models with the integral indicator co
<4. Getting Started>4-3IM 01C25T04-01EN(3) Ident NumberRefer to section 4.5 for explanation of Ident Number.(a) Conrmation by the name p
iIM 01C25T04-01ENDPharpPROFIBUS PA Communication TypeIM 01C25T04-01EN 1st Edition1st Edition: May 2013 (YK)All Rights Reserved, Copyright © 2013, Yoko
<4. Getting Started>4-4IM 01C25T04-01EN4.5 Integration of GSD le and IDENT NumberThe GSD le and Ident number are necessary for PROFIBUS
<5. Parameter Setting>5-1IM 01C25T04-01EN5. Parameter Setting5.1 Easy SetupIMPORTANTAfter setting and sending data with the conguration
<5. Parameter Setting>5-2IM 01C25T04-01EN5.1.3 Output Mode (Characterization Type) The Output Mode (Characterization Type) is set as speci
<5. Parameter Setting>5-3IM 01C25T04-01EN5.2.1 Pressure Calibration(1) Zero Point AdjustmentZero Point Adjustment can be performed in sev
<5. Parameter Setting>5-4IM 01C25T04-01ENa. Auto AdjustmentApplying reference pressure of 0% and 100% of the measurement range to the trans
<5. Parameter Setting>5-5IM 01C25T04-01EN(4) Reset Adjustment to Factory SettingThe Clear Calibration method can reset the adjustment to t
<5. Parameter Setting>5-6IM 01C25T04-01EN5.3.3 Signal CharacterizerBelow is the example of performing the signal characterizer as shown in
<5. Parameter Setting>5-7IM 01C25T04-01EN<5> To conrm entered coordinate.• Procedure to call up the displayDTM [Device] → Congurat
<5. Parameter Setting>5-8IM 01C25T04-01ENTable 5.3 Symbols# Symbol Description1 Nc Unit convert factor2 Kfactor Basic ow Calculation fact
<5. Parameter Setting>5-9IM 01C25T04-01ENTable 5.6 Flow Parameter of ExampleT0503.aiCεβdDρb /4NcSymbol0.60430.9840.60.03162 m0.0527 m1.25
iiIM 01C25T04-01EN5.3 Input Signal Setup ... 5-55.3.1 Low
<5. Parameter Setting>5-10IM 01C25T04-01EN5.4 Output Signal Setup5.4.1 Fail Safe ModeFail Safe Mode denes the Output Value and Status (Q
<5. Parameter Setting>5-11IM 01C25T04-01EN5.5 Local Display5.5.1 Procedure to Set the Integral IndicatorF0505.aiCorresponding decimal po
<5. Parameter Setting>5-12IM 01C25T04-01ENa. Display SelectionA cycle of up to four displays can be shown by assigning variables to the par
<5. Parameter Setting>5-13IM 01C25T04-01ENh. Bar GraphON/OFF setting of Bar Graph in upper eld of integral indicator can be performed by B
<6. Explanation of Basic Items>6-1IM 01C25T04-01EN6. Explanation of Basic Items6.1 OutlineThis chapter describes brief explanation of the
<6. Explanation of Basic Items>6-2IM 01C25T04-01EN6.2.2 Target ModeThe Block modes permitted for the SENSOR transducer block are Automatic
<6. Explanation of Basic Items>6-3IM 01C25T04-01ENComponent name ContentsBar graph Shows the value displayed in the center eld for numeric
<6. Explanation of Basic Items>6-4IM 01C25T04-01ENIndex Unit Display1000 K Kelvin1001 °C degC1002 °F degF1010 m m1011 km km1012 cm cm
<6. Explanation of Basic Items>6-5IM 01C25T04-01ENIndex Unit Display1358 ft3/h ft3/h1359 ft3/d ft3/d1360 ft3/min std. SCFM1361 ft3/h std. S
<6. Explanation of Basic Items>6-6IM 01C25T04-01EN6.4 AI Function BlockThe AI function block is a unit of the software. During execution,
iiiIM 01C25T04-01EN7.3 Simulation Function ...7-27.3.1 Sensor
<6. Explanation of Basic Items>6-7IM 01C25T04-01EN6.4.2 Target ModeThe Target modes permitted for the AI function block are Automatic (Aut
<6. Explanation of Basic Items>6-8IM 01C25T04-01EN6.5.3 Totalizer Value Set (SET_TOT)Reset of the internal value of the function block alg
<7. In-Process Operation>7-1IM 01C25T04-01EN7. In-Process OperationThis chapter describes the procedure performed when changing the operat
<7. In-Process Operation>7-2IM 01C25T04-01EN7.2.3 Alarm Mask FunctionTable 7.1 shows the parameters related to the masking of alarms. User
<7. In-Process Operation>7-3IM 01C25T04-01EN7.3.1 Sensor Transducer BlockIt is necessary to set parameters as shown in Table 7.2 when the
<7. In-Process Operation>7-4IM 01C25T04-01EN7.4 Write lock (Write-protect) functionThe transmitter is provided with a write lock (write-pr
<7. In-Process Operation>7-5IM 01C25T04-01ENF0705.aiIntegral indicatorLocal operation switch(Push-button)Note 1: Use a thin bar which has a
<8. Diagnostic Information>8-1IM 01C25T04-01EN8. Diagnostic Information8.1 Device StatusDiagnostic information and failures are indicated
<8. Diagnostic Information>8-2IM 01C25T04-01ENTable 8.1 Contents of Condensed DIAGNOSISOctet BitDIAGNOSIS MnemonicDescription RemarksNAMUR
<8. Diagnostic Information>8-3IM 01C25T04-01ENTable 8.2 Contents of Classic DIAGNOSISOctet BitDIAGNOSIS MnemonicDescription Remarks1 0 DI
<1. Introduction>1-1IM 01C25T04-01EN1. IntroductionThis manual is for the DPharp EJX/EJA Series Differential Pressure/Pressure Transmitter
<8. Diagnostic Information>8-4IM 01C25T04-01ENTable 8.3 Contents of DIAGNOSIS_EXTENSIONOctet Bit Category Display Message DescriptionNAMU
<8. Diagnostic Information>8-5IM 01C25T04-01EN8.2 Status of Each Parameter in Failure ModeFollowing tables summarize the value of paramete
<8. Diagnostic Information>8-6IM 01C25T04-01ENALARM DisplayCause of AlarmSENSOR Transducer blockNAMUR NE107 CategoryPressure ValuePrimary V
<8. Diagnostic Information>8-7IM 01C25T04-01ENALARM DisplayCause of AlarmSENSOR Transducer blockNAMUR NE107 CategoryPressure ValuePrimary V
<8. Diagnostic Information>8-8IM 01C25T04-01ENTable 8.5 Action of each parameters in failure mode related Sensor Transducer block (Classic
<8. Diagnostic Information>8-9IM 01C25T04-01ENALARM DisplayCause of AlarmSENSOR Transducer blockNAMUR NE107 CategoryPressure Value Primary
<8. Diagnostic Information>8-10IM 01C25T04-01ENTable 8.6 Action of each parameters in failure mode related Function blocks (Condensed stat
<8. Diagnostic Information>8-11IM 01C25T04-01ENALARM DisplayCause of AlarmAI1 Output Value (Channel = Primary Value) Totalizer Value (Chann
<8. Diagnostic Information>8-12IM 01C25T04-01ENALARM DisplayCause of AlarmAI1 Output Value (Channel = Primary Value) Totalizer Value (Chann
<8. Diagnostic Information>8-13IM 01C25T04-01ENTable 8.7 Action of each parameters in failure mode related Function blocks (Classic status
<1. Introduction>1-2IM 01C25T04-01EN1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the syst
<8. Diagnostic Information>8-14IM 01C25T04-01ENALARM DisplayCause of AlarmAI1 Output Value (Channel = Primary Value) Totalizer Value (Chann
<9. Parameter Lists>9-1IM 01C25T04-01EN9. Parameter ListsNote: The Write Mode column contains the modes in which each parameter is write
<9. Parameter Lists>9-2IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeInitial Value Explanation22 38 DEVICE_INSTAL_DATEAUTO Date of
<9. Parameter Lists>9-3IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeInitial Value Explanation72 88 PRIVATE_9 — — Not used for the
<9. Parameter Lists>9-4IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeInitial Value Explanation25 41 PROCESS_CONNECTION_TYPEO/S Unk
<9. Parameter Lists>9-5IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeInitial Value Explanation71 87 STATIC_PRESSURE_LOW_VALUE— —72
<9. Parameter Lists>9-6IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeInitial Value Explanation176 192 TEST_16 — — Not used for the
<9. Parameter Lists>9-7IM 01C25T04-01ENRelative IndexIndex ParameterWrite ModeValid RangeInitial Value Explanation13 29 UNIT_SEL1 AUTO 0-1
<9. Parameter Lists>9-8IM 01C25T04-01EN9.4 AI Function BlockRelative IndexIndex ParameterWrite ModeInitial Value Explanation0 16 BLOCK_OBJ
<9. Parameter Lists>9-9IM 01C25T04-01EN9.5 Totalizer Function BlockRelative IndexIndex ParameterWrite ModeInitial Value Explanition0 16 BL
<1. Introduction>1-3IM 01C25T04-01EN1.2 Warranty• The warranty shall cover the period noted on the quotation presented to the purchaser a
<10. General Specications>10-1IM 01C25T04-01EN10. General Specications10.1 Standard SpecicationsFor items other than those described b
<10. General Specications>10-2IM 01C25T04-01EN10.2 Optional SpecicationsFor items other than those described below, refer to each User’s
<Appendix 1. List of DTM Menu>A1-1IM 01C25T04-01ENAppendix 1. List of DTM MenuA1.1 Parameter Table• Process Variables• Pressure Raw Value
<Appendix 1. List of DTM Menu>A1-2IM 01C25T04-01EN• Easy Setup • TAG• Descriptor• Message• Installation Date• Sensor Transducer Block• Anal
<Appendix 1. List of DTM Menu>A1-3IM 01C25T04-01EN• Calibration• Target Mode• Pressure Calibration• Static Pressure Calibration• Clear Cali
<Appendix 1. List of DTM Menu>A1-4IM 01C25T04-01EN• Input• Static Revision No• Target Mode• Actual Mode• Device Information• Sensor Transdu
<Appendix 1. List of DTM Menu>A1-5IM 01C25T04-01EN• Output• Analog Input 1• Analog Input 2• Analog Input 3• Totalizer• Static Revision No.•
<Appendix 1. List of DTM Menu>A1-6IM 01C25T04-01EN• Local Display• Static Revision No.• Target Mode• Actual Mode• Bar Graph• Display Cycle•
<Appendix 2. List of PDM (EDD) Menu>A2-1IM 01C25T04-01ENAppendix 2. List of PDM (EDD) MenuA2.1 Menu Bar• Save• Delete• Value comparison..
<Appendix 2. List of PDM (EDD) Menu>A2-2IM 01C25T04-01EN• Simulation• Simulation Enable Message • Physical Block• Sensor Transducer Block•
<1. Introduction>1-4IM 01C25T04-01EN1.3 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<Appendix 2. List of PDM (EDD) Menu>A2-3IM 01C25T04-01EN• Sensor Calibration• Pressure Calibration• Static Pressure Calibration• Clear Cali
<Appendix 2. List of PDM (EDD) Menu>A2-4IM 01C25T04-01EN• Characterization • Characterization• Linearization• Linearization Table• Target M
<Appendix 2. List of PDM (EDD) Menu>A2-5IM 01C25T04-01EN• Display • Sensor Value• Value and Status• Function Block 1 - Analog Input• Functi
<Appendix 2. List of PDM (EDD) Menu>A2-6IM 01C25T04-01EN• Alarm States • Function Block 1 - Analog Input• Function Block 2 - Analog Input•
<Appendix 2. List of PDM (EDD) Menu>A2-7IM 01C25T04-01ENA2.2 Parameter Table• Easy Setup• TAG• Descriptor• Message• Installation Date• Sen
<Appendix 2. List of PDM (EDD) Menu>A2-8IM 01C25T04-01EN• Input• Sensor Transducer Block• Static Revision No.• Target Mode• Actual Mode• Tr
<Appendix 2. List of PDM (EDD) Menu>A2-9IM 01C25T04-01EN• Output• Function Block 1- Analog Input • Function Block 2- Analog Input • Functio
<Appendix 2. List of PDM (EDD) Menu>A2-10IM 01C25T04-01EN• Sensor Calibration • Pressure Calibration• Static Pressure Calibration• Lower Ca
<Appendix 2. List of PDM (EDD) Menu>A2-11IM 01C25T04-01EN• Target Mode• Physical Block• Sensor Transducer Block• LCD Transducer Block• Func
iIM 01C25T04-01ENRevision Information Title : DPharp PROFIBUS PA Communication Type (EJXA, EJAE) Manual No. : IM 01C25T04-01ENEditio
<2. Handling Cautions>2-1IM 01C25T04-01EN2. Handling Cautions2.1 Installation of an Explosion-Protected InstrumentIf a customer makes a r