Instruction
Manual
Yokogawa Electric Corporation
Model EJA118W, EJA118N and
EJA118Y Diaphragm Sealed
Differential Pressure Transmitters
[Style: S2]
IM 1C22H1-01E
IM 1C22H1-01E
10th Edition
Vue de la page 0
1 2 3 4 5 6 ... 75 76

Résumé du contenu

Page 1 - Instruction

InstructionManualYokogawa Electric CorporationModel EJA118W, EJA118N andEJA118Y Diaphragm SealedDifferential Pressure Transmitters[Style: S2]IM 1C22H1

Page 2 - Blank Page

IM 1C22H1-01E2-22. HANDLING CAUTIONS2.4 Selecting the InstallationLocationThe transmitter is designed to withstand severeenvironmental conditions. Ho

Page 3 - CONTENTS

IM 1C22H1-01E2-32. HANDLING CAUTIONS2.8 Insulation Resistance andDielectric Strength TestSince the transmitter has undergone insulation resis-tance a

Page 4

IM 1C22H1-01E2-42. HANDLING CAUTIONS• Intrinsically Safe Apparatus Parameters[Groups C, D, E, F and G]Vmax = 30 V Ci = 22.5 nFImax = 225 mA Li = 730

Page 5

IM 1C22H1-01E2-52. HANDLING CAUTIONSNote 4. Maintenance and Repair• The instrument modification or parts replacementby other than authorized represe

Page 6

IM 1C22H1-01E2-62. HANDLING CAUTIONSNote 2. Wiring• All wiring shall comply with Canadian ElectricalCode Part I and Local Electrical Codes.• In hazar

Page 7 - 1. INTRODUCTION

IM 1C22H1-01E2-72. HANDLING CAUTIONS(Zone 0)EJA SeriesPressureTransmitterSafety Barrier *1Hazardous Location Nonhazardous Location+ – + – [Intrin

Page 8 - WARRANTY

IM 1C22H1-01E2-82. HANDLING CAUTIONSb. CENELEC (KEMA) Flameproof TypeCaution for CENELEC (KEMA) flameproof type.Note 1. Model EJA Series differentia

Page 9 - 2. HANDLING CAUTIONS

IM 1C22H1-01E2-92. HANDLING CAUTIONS2.9.5 JIS CertificationJIS Flameproof and Intrinsically Safe TypeThe model EJA Series pressure transmitters witho

Page 10 - IMPORTANT

IM 1C22H1-01E3-13. COMPONENT NAMES3. COMPONENT NAMESTransmitter section**See below for details.Pressure-detector sectionCover flangeDiaphragm seal(hi

Page 11 - Protected Type

IM 1C22H1-01E4-14. INSTALLATION4. INSTALLATION4.1 Precautionsj Before installing the transmitter, read the cautionarynotes in Section 2.4, “Selecting

Page 13 - 2.9.2 CSA Certification

IM 1C22H1-01E4-24. INSTALLATION4.3 Transmitter Mountingj The transmitter can be mounted on a nominal 50mm (2-inch) pipe using the mounting bracketsup

Page 14 - 2.9.3 SAA Certification

IM 1C22H1-01E4-34. INSTALLATION4.4 Affixing the Teflon FilmThe FEP Teflon option includes a teflon film andfluorinated oil.Before mounting the diaphr

Page 15 - Certification

IM 1C22H1-01E5-15. WIRING5. WIRING5.1 Wiring PrecautionsIMPORTANT• Lay wiring as far as possible from electricalnoise sources such as large capacity

Page 16 - F0209.EPS

IM 1C22H1-01E5-25. WIRING5.3.3 BRAIN TERMINAL BT200 Connec-tionConnect the BT200 to the SUPPLY + and – terminals(Use hooks).Transmitter terminal boxB

Page 17 - 2.10 EMC Conformity Standards

IM 1C22H1-01E5-35. WIRING5.4.2 Wiring Installation(1) General-use Type and Intrinsically SafeTypeMake cable wiring using metallic conduit or water-pr

Page 18 - 3. COMPONENT NAMES

IM 1C22H1-01E5-45. WIRINGj Flameproof metal conduit wiring• A seal fitting must be installed near the terminal boxconnection port for a sealed constr

Page 19 - 4. INSTALLATION

IM 1C22H1-01E6-16. OPERATION6. OPERATION6.1 Preparation for Starting Op-erationThe Model EJA118W, EJA118N and EJA118Ydiaphragm sealed differential pr

Page 20 - 4.3 Transmitter Mounting

IM 1C22H1-01E6-26. OPERATION6.2 Zero Point AdjustmentAdjust the zero point after operating preparation iscompleted.IMPORTANTDo not turn off the power

Page 21 - 4.4 Affixing the Teflon Film

IM 1C22H1-01E6-36. OPERATIONj Using the Transmitter Zero-AdjustmentScrewTurn the screw to match the output signal to the actualmeasured value in %.j

Page 22 - 5. WIRING

IM 1C22H1-01E6-46. OPERATION6.5 Setting the Range Using theRange-setting SwitchWith actual pressure being applied to the transmitter,the range-settin

Page 23 - 5.4 Wiring

iCONTENTSIM 1C22H1-01EFD No. IM 1C22H1-01E10th Edition: Feb. 2000(YK)All Rights Reserved, Copyright © 1995, Yokogawa Electric CorporationCONTENTS1. IN

Page 24 - 5.4.2 Wiring Installation

IM 1C22H1-01E7-17. BRAIN TERMINAL BT200 OPERATION7. BRAIN TERMINAL BT200OPERATIONThe DPharp is equipped with BRAIN communicationscapabilities, so tha

Page 25 - Transmitter terminal box

IM 1C22H1-01E7-27. BRAIN TERMINAL BT200 OPERATION7.2.2 Operating Key Functions(1) Alphanumeric Keys and Shift KeysYou can use the alphanumeric keys i

Page 26 - 6. OPERATION

IM 1C22H1-01E7-37. BRAIN TERMINAL BT200 OPERATION7.2.3 Calling Up Menu Addresses Using the Operating KeysDATA DIAG PRNT ESCPARAM A60:SELF CHECK

Page 27

IM 1C22H1-01E7-47. BRAIN TERMINAL BT200 OPERATION7.3 Setting Parameters Using the BT2007.3.1 Parameter SummaryInstruments to which applicable:F: Diff

Page 28 - 6.4 Shutting Down Operation

IM 1C22H1-01E7-57. BRAIN TERMINAL BT200 OPERATIONT0706.EPSAuxiliary setting data 1D Menu nameAUX SET 1—NORMAL/REVERSENORMAL/REVERSE**Output reversalD

Page 29 - F0607.EPS

IM 1C22H1-01E7-67. BRAIN TERMINAL BT200 OPERATION7.3.2 Parameter Usage and SelectionBefore describing the procedure for setting parameters,we present

Page 30 - OPERATION

IM 1C22H1-01E7-77. BRAIN TERMINAL BT200 OPERATION7.3.3 Setting ParametersSet or change the parameters as necessary. Aftercompleting these, do not fai

Page 31 - Alphanumeric keys

IM 1C22H1-01E7-87. BRAIN TERMINAL BT200 OPERATIONb. Setting Calibration Range LowerRange Value and Higher Range Value(C21: LOW RANGE, C22: HIGHRANGE)

Page 32 - F0709.EPS

IM 1C22H1-01E7-97. BRAIN TERMINAL BT200 OPERATION(4) Output Mode and Integral Indicator Dis-play Mode Setup (C40: OUTPUT MODE)The mode setting for th

Page 33 - 7.3.1 Parameter Summary

IM 1C22H1-01E7-107. BRAIN TERMINAL BT200 OPERATION(6) Integral Indicator Scale SetupThe following 5 displays are available for integralindicators.T07

Page 34 - IM 1C22H1-01E

iiCONTENTSIM 1C22H1-01E6. OPERATION... 6-16.1 Preparati

Page 35 - T0707.EPS

IM 1C22H1-01E7-117. BRAIN TERMINAL BT200 OPERATIONb. Setting User-set Engineering Unit(D21: DISP UNIT)This parameter allows entry of the engineering

Page 36 - 7.3.3 Setting Parameters

IM 1C22H1-01E7-127. BRAIN TERMINAL BT200 OPERATION(8) Unit Setup for Displayed Static Pressure(D31: STAT.P.UNIT)Follow the procedure below to change

Page 37

IM 1C22H1-01E7-137. BRAIN TERMINAL BT200 OPERATION(13) Bi-directional Flow Measurement Setup(E30: BI DIRE MODE)(a) This parameter enables selection o

Page 38 - F0718.EPS

IM 1C22H1-01E7-147. BRAIN TERMINAL BT200 OPERATIONNote that changing the higher range value does notcause the lower range value to change but does ch

Page 39 - User-set engineering

IM 1C22H1-01E7-157. BRAIN TERMINAL BT200 OPERATION(b)-2 Follow the procedure below to use J11: ZERODEV.ECSESCSET J11:ZERO DEV. 2.50 %

Page 40 - Press the (OK) key

IM 1C22H1-01E7-167. BRAIN TERMINAL BT200 OPERATION7.4 Displaying Data Using theBT2007.4.1 Displaying Measured DataThe BT200 can be used to display me

Page 41 - F0726.EPS

IM 1C22H1-01E7-177. BRAIN TERMINAL BT200 OPERATION• Example 3: Checking the history of the errorsConnect the BT200 to the transmitter, and call item

Page 42

IM 1C22H1-01E7-187. BRAIN TERMINAL BT200 OPERATION7.5.2 Errors and CountermeasuresThe table below shows a summary of error messages.Table 7.5.1 Error

Page 43

IM 1C22H1-01E8-18. MAINTENANCE8. MAINTENANCE8.1 OverviewWARNINGSince the accumulated process fluid may betoxic or otherwise harmful, take appropriate

Page 44

IM 1C22H1-01E8-28. MAINTENANCETable 8.2.1 Tools for Disassembly and ReassemblyName RemarksYokogawa-recommended InstrumentPower supplyModel SDBT or SD

Page 45 - 7.5.1 Checking for Problems

iiiCONTENTSIM 1C22H1-01E8. MAINTENANCE... 8-18.1 Overview ..

Page 46 - Indicator

IM 1C22H1-01E8-38. MAINTENANCE8.4 Disassembly and Reassem-blyThis section describes procedures for disassembly andreassembly for maintenance and comp

Page 47 - T0711 .EPS

IM 1C22H1-01E8-48. MAINTENANCE8.4.2 Replacing the CPU AssemblyThis subsection describes the procedure for replacingthe CPU assembly. (See Figure 8.4.

Page 48 - 8. MAINTENANCE

IM 1C22H1-01E8-58. MAINTENANCE8.5 TroubleshootingIf any abnormality appears in the measured values, usethe troubleshooting flow chart below to isolat

Page 49 - F0801.EPS

IM 1C22H1-01E8-68. MAINTENANCEConnect BRAIN TERMINAL and check self-diagnostics.Does the self-diagnostic indicate problemlocation?Contact Yokogawa se

Page 50 - 8.4 Disassembly and Reassem

IM 1C22H1-01E9-19. GENERAL SPECIFICATIONS9. GENERAL SPECIFICATIONS9.1 Standard SpecificationsRefer to GS 1C22T2-E for Fieldbus communica-tion type ma

Page 51 - 8. MAINTENANCE

IM 1C22H1-01E9-29. GENERAL SPECIFICATIONSd Physical SpecificationsWetted Parts Materials:Diaphragm and other wetted parts;See ‘Model and Suffix Codes

Page 52 - 8.5 Troubleshooting

IM 1C22H1-01E9-39. GENERAL SPECIFICATIONS9.2 Model and Suffix Codesd Model EJA118W [Style: S2]. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 53 - F0806.EPS

IM 1C22H1-01E9-49. GENERAL SPECIFICATIONSd Model EJA118N [Style: S2]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-D . . . . . .

Page 54 - 9. GENERAL SPECIFICATIONS

IM 1C22H1-01E9-59. GENERAL SPECIFICATIONSd Model EJA118Y [Style: S2]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-D . . . . .

Page 55

IM 1C22H1-01E9-69. GENERAL SPECIFICATIONS9.3 Optional SpecificationsItem Description CodeFactory Mutual (FM)CSA Explosionproof ApprovalExplosionproof

Page 57 - 2 = 150 mm

IM 1C22H1-01E9-79. GENERAL SPECIFICATIONSItem Description CodeT0908.EPSGold-plated diaphragmTTeflon film (Note 3)With FEP film and fluorinated oilWor

Page 58

IM 1C22H1-01E9-89. GENERAL SPECIFICATIONS9.4 Dimensionsd Model EJA118W [Style: S2]Highpressureside34(1.34)Wetted parts materialcode U (Titanium)Lowpr

Page 59 - 9.3 Optional Specifications

IM 1C22H1-01E9-99. GENERAL SPECIFICATIONSd Model EJA118N [Style: S2]ø30(1.18)120(4.72)X214(0.55)tfLowpressuresiden-øhøDøAøgøC333(13.11)140(5.51)94(3.

Page 60

IM 1C22H1-01E9-109. GENERAL SPECIFICATIONSd Model EJA118Y [Style: S2]HighpressuresideLowpressuresideø78(3.07)ZeroadjustmentGroundterminalTerminalside

Page 61 - 9.4 Dimensions

EX-A03E1INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENTINSTALLATION AND OPERATING PRECAUTIONS FORJIS INTRINSICALLY SAFE EQ

Page 62 - Unit : mm (approx.inch)

EX-A03E2INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENT— when up to two countable faults are applied and, inaddition,— whe

Page 63 - F0904.EPS

EX-A03E3INSTALLATION AND OPERATING PRECAUTIONS FOR JIS INTRINSICALLY SAFE EQUIPMENTintrinsically safe apparatus may be used at an ambienttemperature u

Page 64

EX-B03E1INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENTINSTALLATION AND OPERATING PRECAUTIONS FORJIS FLAMEPROOF EQUIPMENTApparatus

Page 65

EX-B03E2INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT4. Installation of FlameproofApparatus(1) Installation AreaFlameproof appar

Page 66

EX-B03E3INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT6. Maintenance of FlameproofApparatusTo maintain the flameproof apparatus,

Page 67 - JIS FLAMEPROOF EQUIPMENT

IM 1C22H1-01E1-11. INTRODUCTION1. INTRODUCTIONThank you for purchasing the DPharp electronicpressure transmitter.The DPharp Pressure Transmitters are

Page 69

CustomerMaintenanceParts ListAll Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation.Yokogawa Electric CorporationCMPL 1C22A1-02E6th Edit

Page 70

2CMPL 1C22A1-01ESubject to change without notice. Printed in Japan.Blank Page

Page 71 - Parts List

CustomerMaintenanceParts ListAll Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation.Yokogawa Electric CorporationCMPL 1C22H1-01E3rd Edit

Page 72

2CMPL 1C22H1-01EOct. 1999Subject to change without notice. Printed in Japan.123456789F9300AJ——BelowY9625YUY9630YUY9640YUY9635YUY9612HUBelowF9270AWF93

Page 73

IM 1C22H1-01EREVISION RECORDTitle: Model EJA118W, EJA118N, and EJA118Y Diaphragm Sealed DifferentialPressure TransmitterManual No.: IM 1C22H1-01EEditi

Page 74 - CMPL 1C22H1-01E

IM 1C21B1-01EEdition Date Page Revised ItemREVISION RECORD.EPS–9-7CMPL–9-3CMPL 1C22A1-02E 5th 6thCMPL 1C22H1-01E 3rd• Installation and Operating

Page 75 - REVISION RECORD

IM 1C22H1-01E1-21. INTRODUCTIONWARRANTY• The warranty shall cover the period noted on thequotation presented to the purchaser at the time ofpurchase.

Page 76 - REVISION RECORD.EPS

IM 1C22H1-01E2-12. HANDLING CAUTIONS2. HANDLING CAUTIONSThis chapter describes important cautions regardinghow to handle the transmitter. Read carefu