<4. Engineering>
4-14
IM 11B06E01-01E 4th Edition : Nov. 22, 2011-00
TIP
IPaddressofASGWintheredundantnetworkmustbesetupfrom192.168.0.1to192.168.0.126.
4.3.2 Modicationofserialportsetting
InthecaseofusingtheModbusRTUasexternalinterfaceofASIU/ASGW,thisoperationis
required.
ASGW has two communication ports and both initial setting data are as follows.
Baudrate =9600
DataBitLength =8
StopBitLength =1
Parity =NONE
After ASIU/ASGW mode is changed to maintenance mode, the communication port is set with
the maintenance window on web browser.
RefertotheguideofSTARDOMFCN/FCJ(IM34P02Q01-01E)aboutthemethodofmodica-
tion.
Settingparametersare“COM1PortSettingFile”or“COM2PortSettingFile”.
4.3.3 Allocating DO information
Allocate the device label of ASGW to the DO terminal before outputting DO information of the
ASGW application to the terminal. The device label of ASGW is the default factory setting.
(1)ConrmingthecurrentstateoftheASGWapplication
ConrmthattheASGWapplicationhasbeensuccessfullydownloaded.Afterconnectingbyusing
ResourceCongurator,clicktheControlApplication/DevLabelVar.Then,conrmthatthevalue
ofI/OCategoryisO_StsandthevalueofDeviceLabelisQ_D_17toQ_D_32,asshowninthe
followinggure.